Lennox · Furnace

10 Unknown device detected

High severity

What the control is telling you

Outside of commissioning, the thermostat found a device it does not know and put it in soft disable (two horizontal lines on furnace/air handler/outdoor 7-segment display; green LED 3 s on / 1 s off on damper module or EIM). S30/S40 thermostat alert code 10.

Applies to: Lennox communicating gas furnaces (e.g. SL280UHV/SL280UHNV, EL296UHV) in S30/S40 smart thermostat systems

Likely causes

  • A new communicating device was added after the original setup
  • A control board was replaced and the system was not reconfigured

Test and repair steps

  1. Find the soft-disabled control (two horizontal lines on its display, or green LED 3 s on / 1 s off).
  2. Confirm the added device is Lennox communicating compatible.
  3. S30 go to Menu > Settings > Advanced Settings, open View Dealer Control Center, then pick Equipment > Reset All Equipment. The thermostat will find every Lennox communicating device again.
  4. S40 go to Menu > Settings > Advanced Settings, open View Service Support Center, then Equipment Setting > Reset and pick Reset HVAC Equipment.
  5. Clear reconfigure the system (code clears after reconfiguration).

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.8. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.