Lennox · Furnace
E291 Heat airflow below minimum
What the control is telling you
Heating airflow is restricted below minimum; 1-hour soft lockout.
Applies to: EL296UHV(X) series furnaces with integrated control 103130-XX only
Likely causes
- Dirty filter
- Duct restriction
- Blower performance problem
Test and repair steps
- Inspect the filter (should be checked monthly) and replace if dirty; oversized pressure drop from high-efficiency filters can trip the limit.
- Measure external static pressure heating speed must not exceed 0.8 in. w.c.
- Measure temperature rise (supply minus return) and confirm it is within the rating-plate range, adjusting blower heat speed (DIP 11-13) if needed.
- Check the blower wheel for debris and verify blower operation.
- Clears when a heat call completes successfully.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox SL297NV
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.36. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.