Lennox · Furnace

E292 Blower motor will not start

High severity EL296UHVLennox SL280UHVLennox SL297NV

What the control is telling you

Indoor blower motor cannot start (seized bearings, stuck/obstructed wheel). 1-hour soft lockout.

Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)

Likely causes

  • Seized motor bearings
  • Obstructed blower wheel
  • Failed motor

Test and repair steps

  1. Warning: Disconnect power before working on the blower.
  2. Spin the blower wheel by hand; check for obstruction or rubbing.
  3. Test motor windings resistance to ground must be over 100k ohms; each phase-to-phase reading under 20 ohms and equal.
  4. Replace motor or wheel if the assembly does not run or perform correctly.
  5. Clears once the blower starts successfully.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.36; Ignition Control 107045-XX Diagnostic Codes table, p.43. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.