E311 Heat rate reduced for airflow

Medium severity EL296UHVLennox SL280UHVLennox SL297NV

What the control is telling you

Warning only: blower is in cutback due to restricted airflow, so firing rate is reduced every 60 seconds to match available CFM (2-stage controls drop to 1st stage).

Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)

Likely causes

  • Dirty filter
  • Undersized or restricted ductwork

Test and repair steps

  1. Check and replace the filter if dirty.
  2. Inspect the duct system for restrictions; repair or add duct as needed.
  3. Clears when a heat call completes successfully.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.36; Ignition Control 107045-XX Diagnostic Codes table, p.43. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.