Lennox · Furnace
E270 Soft lockout - no flame after max retries
What the control is telling you
Ignition retries exhausted without sensing flame.
Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)
Likely causes
- No gas or low gas pressure
- Ignitor not lighting burners
- Flame sensor not sensing
Test and repair steps
- Warning: Do not try to light the burners by hand; smell for gas near the floor before working on the unit.
- Know the sequence inducer 15 s pre-purge, 20 s ignitor warm-up, then gas valve opens on low fire and flame must be sensed within 4 seconds; failed trials get a 15 s inter-purge, and after the 5th failed trial the control goes into Watchguard (auto-reset after 1 hour).
- Confirm gas is on at the meter, the manual shut-off valve and the gas valve switch; purge air from the line on a new start-up.
- Check gas pressures with a manometer supply natural gas 4.5-13.0 in. w.c. (LP 11.0-13.0); manifold natural 1.7 low fire / 3.5 high fire (LP 4.5 / 10.0) at 0-4500 ft.
- Watch a trial verify the ignitor glows and burners light. Check ignitor resistance at the control (terminals 1 and 5): 39-70 ohms, and 120 V +/-10% during warm-up.
- Check flame current in F mode (2.6 uA or more normal; drop-out at 1.1 uA); clean or replace the flame sensor.
- Check ground at the control AC volts between line neutral and the C terminal should not exceed 2 VAC at idle, 5 VAC with inducer/ignitor on, 10 VAC with blower on; a wide swing under load means a poor ground. Line hot to neutral should be 97-132 VAC.
- If burners are dirty, shut off power and gas, remove the burner box and vacuum the burner faces with a soft brush, then realign burners to the ports.
- Clears after a successful heat call; Watchguard also resets after 1 hour of continuous demand, or cycle the thermostat/power.
Settings for these units
Recommended filter size by cabinet width · EL296UHV
| Cabinet width | Side return | Bottom return |
|---|---|---|
| 17-1/2 in. | 16 x 25 x 1 in. (1) | 16 x 25 x 1 in. (1) |
| 21 in. | 16 x 25 x 1 in. (1) | 20 x 25 x 1 in. (1) |
| 24-1/2 in. | 16 x 25 x 1 in. (2) | 24 x 25 x 1 in. (1) |
Number in brackets is the quantity of filters.
Filters are field supplied and installed outside the furnace; inspect monthly.
Recommended filter size by cabinet width · Lennox SL280UHV
| Cabinet width | Side return | Bottom return |
|---|---|---|
| 14-1/2 in. | 16 x 25 x 1 in. (1) | 14 x 25 x 1 in. (1) |
| 17-1/2 in. | 16 x 25 x 1 in. (1) | 16 x 25 x 1 in. (1) |
| 21 in. | 16 x 25 x 1 in. (1) | 20 x 25 x 1 in. (1) |
| 24-1/2 in. | 16 x 25 x 1 in. (2) | 24 x 25 x 1 in. (1) |
Number in brackets is filter quantity; filters are field supplied.
Never run the unit without a filter installed.
- Filter sizes by cabinet width · Lennox ML180UHE
- Filter sizes by cabinet width · Lennox SL297NV
Models that show this code
34 models in EL296UHV, Lennox SL280UHV, Lennox ML180UHE, Lennox SL297NV
Other codes on the same units
- E240 Low flame current (run mode)
- E241 Flame sensed out of sequence - flame present
- E250 Limit switch circuit open
- E252 Discharge air temperature too high
- E271 Soft lockout - retries exceeded, pressure switch opened
- E272 Soft lockout - recycles exceeded, pressure switch opened
- E273 Soft lockout - recycles exceeded, flame failure
- E274 Soft lockout - limit opened
Sequence of operation
What the unit does around this code, step by step.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.35; Ignition Control 107045-XX Diagnostic Codes table, p.42, Troubleshooting: Heating Sequence of Operation flowchart, p.110-112, Heating System Service Checks p.82-85, Maintenance p.88-89. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.