Lennox · Furnace · Heating
Two-stage variable speed furnace heating with two-stage thermostat
What happens, in order
- Thermostat first-stage heat call closes; control self-checks, confirms limits closed and pressure switches open
- Inducer starts on low speed
- When the low pressure switch closes, a 15 second pre-purge runs on low speed
- If the low fire pressure switch does not close, the inducer goes to high fire; after the 15 second pre-purge the high fire switch closes and the furnace starts on high fire, then drops to low fire after 10 to 20 seconds
- 20 second ignitor warm-up follows, inducer stays on low
- Gas valve opens on low fire and ignition occurs; the 30 second blower on-delay starts at the same moment
- Blower starts on low heat speed; HUM contacts and the 120 V ACC terminal are energized
- Second-stage call a 30 second recognition delay runs, then the inducer goes to high speed, the control checks the high fire pressure switch, the high fire gas valve opens and the blower moves to high heat speed
- Second stage satisfied inducer drops to low, high fire valve closes, blower goes to low heat speed
- First stage satisfied gas valve closes, 5 second low-speed post-purge, and the selected blower off delay starts
- After post-purge the inducer, HUM and ACC terminals drop; the blower stops at the end of the off delay
Timings and thresholds
| Item | Value |
|---|---|
| Pre-purge | 15 s low speed |
| Ignitor warm-up | 20 s |
| Trial for ignition | 4 s |
| Blower on delay | 30 s |
| Second-stage recognition delay | 30 s (communicating thermostat 15 to 45 s) |
| Post-purge | 5 s low speed |
| Blower off delay | 60, 90 (factory), 120 or 180 s by dip switches 3 and 4 |
Codes you may see during this
Applies to: Two-stage variable-speed Lennox furnaces with dip switch 1 OFF (two-stage thermostat)
Models
More Lennox furnace sequences
- Single-stage furnace ignition retries and watchguard · Ignition
- Two-stage furnace ignition retries and watchguard · Ignition
- Single-stage furnace gas heating cycle · Heating
- Two-stage furnace heating with single-stage thermostat · Heating
- Cooling call on single-stage furnace blower · Cooling
- Two-stage variable speed cooling call · Cooling
- Continuous fan with heat or cool calls · Standby/shutdown
Related
Lennox error codes · Lennox tips · Lennox parts · All Lennox sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Lennox SL280UHV installation manual 508245-01 (04-2024), Heating Sequence of Operation p.46; Lennox SL280UHNV service manual Corp 1601-L8 (rev 04-2024), Sequence of Operation; Lennox SL297UHNV installation manual 507760-02 (02-2018), Heating Sequence of Operation pp.51-52; Lennox EL296UHV installation manual, Ignition and Two Stage Operation pp.27-28. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.