Lennox · Furnace · Heating

Single-stage furnace gas heating cycle

EL195UHNEML180UHEK

What happens, in order

  1. Thermostat calls for heat (W) and the control runs a self-check
  2. Control confirms the primary and secondary limit and the rollout switch are closed, and that the combustion air pressure switch is open
  3. If the pressure switch is already closed, the control will not start the cycle
  4. Inducer starts
  5. When the pressure switch closes, a 15 second pre-purge starts
  6. If the pressure switch has not closed after 2.5 minutes the control goes into pressure switch watchguard for a 5 minute wait, then restarts the sequence
  7. Ignitor warms for 20 seconds; the gas valve opens at the 19 second point and the 4 second trial for ignition begins
  8. Ignitor stays on for the first 3 seconds of the trial
  9. Flame is proven and the gas valve stays open for the rest of the call
  10. Indoor blower starts at heating speed 30 seconds after flame is proven
  11. Thermostat satisfied gas valve closes, inducer runs a 5 second post-purge, and the blower keeps running for the selected off delay
  12. Line voltage below 70 V stops the cycle (EL195 flash 13) until voltage is back above 75 V
  13. Rollout open gas valve off, inducer and blower run, and the control holds until the rollout closes and power or the thermostat call is reset
  14. Primary limit open gas valve off, blower runs on the limit

Timings and thresholds

ItemValue
Pre-purge15 s
Ignitor warm-up20 s
Gas valve opens19 s into warm-up
Trial for ignition4 s
Ignitor on during trialfirst 3 s
Pressure switch prove time2.5 min, then 5 min wait
Blower on delay30 s after flame (not adjustable)
Post-purge5 s
Blower off delay EL19590 s factory, jumper adjustable
Blower off delay ML180120 s factory, 2-position dip switch, 4 choices
Low voltage lockoutbelow 70 V stops, resumes above 75 V (EL195)

Codes you may see during this

EL195 flashes: 1 polarity reversed; 2 poor ground; 7 limit open; 8 rollout open; 9 pressure switch failed to close or opened during call; 10 pressure switch opened 5 times in one call; 11 pressure switch stuck closed; 12 flame without gas valve; 13 low line voltage. ML180: E110, E111, E112, E200, E223, E224, E227, E241, E250

Applies to: EL195UHNE, ML180UHEK gas furnaces with single-stage integrated control

Models

EL195UHNEML180UHEK

More Lennox furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Lennox EL195UHNE service manual Corp 1801-L1 (rev 04-2024), Sequence of Operation pp.9-10 and 49-54; Lennox ML180UHEK service manual 100166, Heating Ignition Sequence p.11 and Sequence of Operation pp.36-40. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.