Lennox · technician tips
Lennox service menus, test modes and resets
80 tips for air conditioner, furnace, gas fireplace, general, heat pump: access codes, button combinations, test modes and the resets you need at the appliance.
Jump to: Access & passwords (3) · Button combinations (2) · Service & test modes (4) · Reset & cancel (6) · Settings shortcuts (20) · Commissioning (14) · Other (31)
Access & passwords
Installer and service menu codes, and how to get into them.
Create a new user account in Lennox Home
General · L40
Account setup in the Lennox Home app. Biometric login is optional and can be chosen at the prompt after registration.
- Open Lennox Home and tap Create New Account.
- Fill in first name, last name, phone, email and password.
- Tick the box to accept the Lennox EULA and tap Register.
- Tap OK on the Sign Up confirmation.
- At the login-save prompt, choose Yes or No for biometric logins.
Applies to: Lennox Home app, L40 Smart Thermostat
Source: L40 User Guide (English), p. 8. Written in our own words; check the manual for your exact model.
Temporary advanced diagnostics access for dealer
General · S40
A dealer can request temporary remote access to run diagnostics. The homeowner must accept the request. Access lasts 24 hours and ends automatically after that. The dealer can only reach the thermostat remotely if the homeowner allowed it or accepted the request. The mobile device needs notifications allowed for the S40 app.
- Homeowner presses Allow on the access request to grant 24-hour dealer access.
- Confirm the Advanced Diagnostics Access Granted dialog and press OK.
- The Advanced Diagnostics in progress badge shows on the Home screen while the dealer is connected. Press it and select More Info to see Technician connected.
- To end access, press the badge, press End Access, press Yes, then press OK. If the dealer is still working, access ends when the service or diagnostics finish.
Applies to: Lennox S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 46-47. Written in our own words; check the manual for your exact model.
Unlock the screen or clean it
General · S40 Smart Thermostat
If the screen is partially or fully locked, press and hold the lock icon for 3 seconds. The lock screen can also be used while wiping the screen clean.
- Press and hold the lock icon for 3 seconds.
- Wipe the screen with the lock screen active if cleaning is needed.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 24. Written in our own words; check the manual for your exact model.
Button combinations
Key presses that open menus, show readouts or switch modes.
Recall or clear the last 10 error codes (red LED button)
Furnace · Lennox EL195UHNE
A button next to the red LED replays the stored error codes, newest first; holding it clears them.
- Press and release the button to start recall (newest code first).
- Watch the red LED flash each code, with a 3 second pause between codes.
- To clear the stored codes, press and hold the button for more than 5 seconds.
Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)
Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10. Written in our own words; check the manual for your exact model.
Unlock the screen
General · S40 Smart Thermostat
Partially Locked and Locked screens need a press and hold on the lock icon to unlock.
- Press and hold the lock icon for 3 seconds.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 24. Written in our own words; check the manual for your exact model.
Service & test modes
Forced fan, low and high fire, test and diagnostic modes, error history and live data.
Simulate a refrigerant leak with the RDS Test button
Air conditioner · Lennox EL16KC1
After the 5-minute purge, pressing Test during a call makes the board act as if a leak was found, which checks wiring and response.
- Restore power and wait for the 5-minute purge to finish.
- Cooling check: start a cooling call at the thermostat, press Test on the RDS board, and confirm the LED flashes blue, the blower runs and the outdoor compressor stops.
- Press Test again to end the simulated leak.
- Heating check (gas furnace): start a heat call, press Test, and confirm the blue flashing LED, blower on, burners off and compressor off. Press Test again to end it.
Applies to: Lennox EL16KC1 A/C with RDS blower control board 27A02 (R-454B)
Source: Lennox EL16KC1 (Elite A-C, R-454B) Installation Instructions 100121 (01-2025), Start-Up Test Procedure (RDS Blower Control Board), printed p.35-36. Written in our own words; check the manual for your exact model.
Test or reset the Low GWP refrigerant detection board (Test button)
Furnace · Lennox ML180UHE
A short press in Normal mode simulates a leak response (E164 for about a minute); in Leak Detected or Fault mode it resets the board after the problem is fixed; while initializing it skips the rest of the pre-purge.
- To test after installation: restore power and wait for the initializing purge to finish.
- Start a cooling or heating call and press the Test button; the blower should start, the compressor should stop (and the burners on a heat call).
- Press Test again to end the simulated leak.
- After a real leak or fault is resolved, press Test to bring the board back to Normal.
Applies to: Lennox ML180UHEK furnaces with Low GWP refrigerant detection control board
Source: Lennox ML180UHEK 100166, Furnace Control Board Low GWP Modes of Operation and LGWP Test Button Functionality (Tables 18-19), printed p.34-35. Written in our own words; check the manual for your exact model.
Respond to advanced diagnostics request
General · S40 Smart Thermostat
The Home screen shows the state of remote dealer access: request pending, access granted, access denied, request expired, diagnostics in progress and access canceled.
- Review the icon on the Home screen.
- Grant or deny access as the homeowner chooses; the dealer can cancel or diagnose remotely.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 22-23. Written in our own words; check the manual for your exact model.
Use the defrost control TEST pins to clear lockouts or force defrost
Heat pump · Lennox EL16KP1, Lennox ML14KP1
A jumper on the TEST pins (P1) clears short cycle and five-strike lockouts and forces the unit into and out of defrost; the 30 s defrost off-delay does not work while it is fitted.
- Place the jumper on the TEST pins of P1.
- Use it to clear the lockout or to cycle the unit in or out of defrost.
- After testing, move the jumper back across the desired defrost termination temperature pins (factory setting 50 F).
Applies to: Lennox EL16KP1 (Elite) and ML14KP1 (Merit) R-454B heat pumps, sizes -018 to -060, demand defrost control A108 (CMC1)
Source: Lennox EL16KP1 Unit Information 100195 / ML14KP1 Unit Information 100108, Defrost Control Connections, Test Pins (P1) Function, p.31. Written in our own words; check the manual for your exact model.
Reset & cancel
Clearing lockouts, service reminders and fault history; skipping purge or de-air programs.
Cancel Away mode
General · S40 Smart Thermostat
Away can be ended from the Home screen or from the Away is Active notice.
- Press Cancel at the bottom left of the Home screen.
- Or tap the Away is Active notice on the right and select Yes to cancel.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 17. Written in our own words; check the manual for your exact model.
Cancel Peak Monitoring enrollment
General · L40 Smart Thermostat
Cancelling enrollment removes the thermostat from the energy savings program.
- Go to Menu > Settings > Peak Monitoring > Energy Savings Settings.
- Select Cancel Enrollment.
Applies to: Lennox L40 Smart Thermostat
Source: Lennox Home (L40) User Guide, p. 20. Written in our own words; check the manual for your exact model.
Manual Away on and off
General · S40 Smart Thermostat
Away mode uses the Away set points. The Away icon turns it on and the Cancel icon turns it off.
- Press the Away icon on the Home screen to start Away mode.
- Press the Cancel icon to leave Away mode.
- Change the Away set points in Menu > Settings > Away.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 28. Written in our own words; check the manual for your exact model.
Postpone Cleaning Air
General · S40 Smart Thermostat
When the Smart Air Quality Monitor flags poor air, the fan runs to clean it. You can postpone the cleaning for a set time.
- Tap the Cleaning Air notice on the Home screen.
- Select Postpone.
- Choose 1, 2, 4, 8 or 24 hours.
Applies to: Lennox Smart Air Quality Monitor
Source: Lennox S40 Smart Thermostat User Guide, p. 22. Written in our own words; check the manual for your exact model.
Reboot the thermostat
General · S40 Smart
Reboot the S40 with a paper clip through the reboot pin hole. Hold for about six seconds. Settings are kept.
- Insert a paper clip into the reboot pin hole on the thermostat.
- Press and hold for about six seconds.
- Release. The thermostat reboots and keeps its settings.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 4. Written in our own words; check the manual for your exact model.
Settings shortcuts
Where the useful parameters live and what they are set to from the factory.
Switch between intermittent and standing pilot (CPI/IPI)
Gas fireplace · Lennox Elite Linear View LDV42/LDV54
The DFC control can run intermittent pilot or standing pilot.
- The CPI/IPI switch is in the control compartment next to the main gas shutoff.
- OFF = intermittent pilot. ON = standing pilot.
Applies to: Elite Linear View LDV42N, LDV42P, LDV54N, LDV54P (SIT Proflame DFC control, remote wall receiver)
Source: Lennox Hearth Elite Linear View Direct-Vent Gas Fireplace LDV42/LDV54 Installation Instructions 506011-02 (06/2012), CPI/IPI Switch p.11; Wiring Diagram p.24. Written in our own words; check the manual for your exact model.
Auto-changeover only works in Heat/Cool mode
General · L40
The thermostat switches between heating and cooling automatically, but only when the system is set to Heat/Cool mode.
- Set the system mode to Heat/Cool to use auto-changeover.
- See the Heat and Cool (Auto-Changeover) section on page 20 for more detail.
Applies to: Lennox L40 smart thermostat
Source: Home (L40) User Guide, p. 3-4. Written in our own words; check the manual for your exact model.
Change set points while in Away
General · S40 Smart Thermostat
Away set points can be changed on the fly from the Home screen.
- Tap the heat-to or cool-to value shown on the Home screen.
- Adjust to the new set point.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 21. Written in our own words; check the manual for your exact model.
Circulation timer range
General · S40 Smart Thermostat
Air circulation can be set from 9 to 27 minutes per hour. Circulate runs in any mode except when the system is off.
- Go to Menu, Settings, Fan.
- Adjust circulation time between 9 and 27 minutes per hour.
Applies to: Lennox S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 32. Written in our own words; check the manual for your exact model.
Current temperature and Feels Like
General · S40 Smart Thermostat
Feels Like uses outdoor temperature, indoor temperature and indoor humidity to show what the space feels like. It is not a setpoint. Smart Room Sensors can be added to the calculation.
- Go to Menu > Settings > Current Temperature.
- Turn Feels Like ON to show it above the indoor temperature on the Home screen.
- Select the Smart Room Sensors to include in averaging, based on occupancy.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 30. Written in our own words; check the manual for your exact model.
Dealer support access options
General · L40
Dealer access features that let the local Lennox dealer see data and diagnose issues remotely.
- Remote Sharing lets the dealer view set points and heating and cooling run times.
- Alerts and Notifications Technician lets the dealer be notified when service or maintenance is needed.
- Advanced Diagnostics lets the homeowner share diagnostics with the dealer for remote troubleshooting.
- Unregister System removes the thermostat from the homeowner email account.
Applies to: L40 Smart Thermostat with Lennox Home
Source: L40 User Guide (English), p. 12. Written in our own words; check the manual for your exact model.
Enable dealer service alerts
General · L40
The homeowner must turn this on before the dealer receives service alerts and alert emails.
- From the home screen, go to Menu > Lennox Dealer Support Access > Dealer Support Access.
- Set Alerts and Notifications Technician to ON.
Applies to: Lennox L40 Smart Thermostat dealer alerts
Source: Home (L40) User Guide, p. 26. Written in our own words; check the manual for your exact model.
Enable homeowner alert emails
General · L40
Email updates must be enabled for the homeowner to receive alert emails.
- From the home screen, go to menu > user account > Alerts and Reports.
- Set Alerts and Notifications - Homeowner to ON.
Applies to: Lennox L40 Smart Thermostat homeowner email alerts
Source: Home (L40) User Guide, p. 26. Written in our own words; check the manual for your exact model.
Enable Smart Zoning control
General · S40 Smart Thermostat
Zoning is ON by default. To run the system in central mode, turn zoning OFF. Zone names can be changed on this screen.
- Go to Menu, Settings, Zoning Control.
- Set zoning OFF to run central mode.
Applies to: Lennox S40 with Smart Zoning System
Source: Lennox S40 Smart Thermostat User Guide, p. 35. Written in our own words; check the manual for your exact model.
Hide the indoor humidity display
General · S40 Smart
The indoor humidity percentage shows on the home screen by default. It can be turned off in the display settings. Keep the humidity sensor intake clear.
- Go to Menu > Setting > Display.
- Turn off the humidity percentage display.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 4. Written in our own words; check the manual for your exact model.
Load a photo screensaver
General · S40 Smart Thermostat
A photo must be uploaded from the app first, then accepted on the thermostat before it shows as the screensaver.
- In the Lennox S40 Thermostat app, go to Menu > Display Settings > Screensaver and upload the image.
- Wait for the upload confirmation screen.
- On the thermostat, go to Menu > Display Settings, turn on Screensaver and select Photo.
- Accept the uploaded photo when prompted.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 24. Written in our own words; check the manual for your exact model.
One Touch Away quick setback
General · L40
Reduces system output and energy use while occupants are away.
- Tap the One Touch Away icon to turn it on.
- Tap the icon again after occupants return to resume the normal heating and cooling schedule.
- Heating and cooling temperatures used while away are set during customization.
Applies to: Lennox L40 smart thermostat
Source: Home (L40) User Guide, p. 3, 7. Written in our own words; check the manual for your exact model.
Set the outdoor temperature source
General · S40 Smart Thermostat
Accuweather is the default outdoor temperature source. It needs a good Wi-Fi and Lennox server connection and a logged-in user account.
- Go to Menu > Display Settings > Home screen settings.
- Choose Accuweather or the outdoor temperature sensor.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 24. Written in our own words; check the manual for your exact model.
Smart Away is paused during manual Away
General · S40 Smart Thermostat
When Away is selected manually, the Smart Away feature is turned off until Away is canceled.
Applies to: S40 Smart Thermostat with Smart Away enabled
Source: Lennox S40 Smart Thermostat User Guide, p. 21. Written in our own words; check the manual for your exact model.
Turn Allergen Defender on or off
General · S40 Smart Thermostat
Allergen Defender runs the fan between heat or cool calls when pollen is high. It needs internet weather enabled and works best with MERV 11 or higher filters. It runs only when On, Auto and Circulate are not in use.
- Go to Menu > Settings > Fan.
- Turn Allergen Defender on or off.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 21. Written in our own words; check the manual for your exact model.
Turn on Auto Brightness
General · S40 Smart
Auto Brightness uses the ambient light sensor to adjust the screen brightness to the room light.
- Go to Menu > Settings > Display.
- Enable Auto Brightness.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 4. Written in our own words; check the manual for your exact model.
Turn on dehumidify
General · S40 Smart Thermostat
Dehumidification runs in cooling mode and uses the user humidity band.
- Go to Menu > Settings > Humidity.
- Turn on dehumidify.
- Adjust the low and high humidity levels with the dehumidification set-point slider.
Applies to: S40 Smart Thermostat with cooling
Source: Lennox S40 Smart Thermostat User Guide, p. 19. Written in our own words; check the manual for your exact model.
Upload and set a screensaver photo
General · S40 Smart Thermostat
A photo must first be uploaded from the Lennox app, then accepted on the thermostat.
- Upload the image from the Lennox S40 Smart Thermostat app under Menu > Display Settings > Screensaver.
- On the thermostat, go to Menu > Display Settings and turn on Screensaver.
- Select Photo and accept the uploaded picture.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 24. Written in our own words; check the manual for your exact model.
Commissioning
Start-up and set-up steps that are easy to miss.
Pair a new remote with the wall receiver
Gas fireplace · Lennox Elite Linear View LDV42/LDV54
The receiver learns a new remote by itself.
- Slide the wall receiver to REMOTE.
- Press ON/OFF on the hand remote.
- Three beeps = paired.
Applies to: Elite Linear View LDV42N, LDV42P, LDV54N, LDV54P (SIT Proflame DFC control, remote wall receiver)
Source: Lennox Hearth Elite Linear View Direct-Vent Gas Fireplace LDV42/LDV54 Installation Instructions 506011-02 (06/2012), Remote Control System p.25-26. Written in our own words; check the manual for your exact model.
Program the unit size code on a replacement furnace control
Furnace · EL296UHV
A replacement control needs the furnace size code stored; three bars then E203 at power-up means no valid code.
- Thermostat OFF and control idle.
- Hold the button until a solid P shows, then release.
- Hold the button again and release when the right size code shows.
- Within 10 s hold the button for 5 s to store it.
- Cycle 24 V power to confirm the code was saved.
Applies to: All EL296UHV models: EL296UH045XV36B, 070XV36B, 090XV36C, 090XV48C, 090XV60C, 110XV48C, 110XV60C, 135XV60D
Source: Lennox EL296UHV(X) Unit Information, Corp 1125-L5 (rev. 03/2022), IX Program Unit Capacity Size Modes, p.110 (printed p.109). Written in our own words; check the manual for your exact model.
Add thermostat to a new user account
General · S40 Smart
If the homeowner has no S40 account, create one in the app first and then pair the thermostat with a PIN.
- Select No on the thermostat and download the Lennox Smart Thermostat app.
- Return to the thermostat and press to continue.
- In the app, tap Create New User Account and complete registration.
- On the thermostat, press to generate a temporary PIN.
- In the app's Add Smart Thermostat screen, press +, enter the PIN and press Add.
- Press OK when the Thermostat Added message appears.
- Create or select a home.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 7. Written in our own words; check the manual for your exact model.
Add thermostat to a user account with an existing account
General · S40 Smart
If the homeowner already has an S40 user account, pair the thermostat to the app with a PIN from the thermostat.
- On the thermostat, answer Yes to the user account question.
- Confirm the Lennox Smart Thermostat app is installed on the phone or tablet.
- In the app, go to Menu and select Add Thermostat.
- On the thermostat, press to generate a PIN.
- Enter the PIN in the app's PIN field and press Add.
- Press OK when the Thermostat Added message appears.
- Create or select a home when prompted.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 7. Written in our own words; check the manual for your exact model.
Create a home in the app
General · S40 Smart
Enter the home details in the app. The home name then shows on the thermostat home screen.
- Select Create New Home and go to the next screen.
- Enter Home Name, Country/Region, Address 1, Address 2, City, State and Zip/Postal Code.
- Press to save. The home screen shows the new home name.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 8. Written in our own words; check the manual for your exact model.
Customization Process
General · S40 Smart
Customization is done only in the Lennox Smart Thermostat app. It walks through about ten screens. Until it is done, a customization badge stays on the home screen.
- Press the customization badge on the thermostat home screen.
- Press Yes in the customization dialog.
- Follow the ten screens in the app to set the top features, starting with the schedule screen.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 8. Written in our own words; check the manual for your exact model.
Customize the thermostat after initial setup
General · L40
After the technician finishes setup, the homeowner can complete customization from the home screen.
- Tap the cogwheel in the lower right corner of the home screen.
- Tap Yes when the Setup Pending screen appears.
- Select the thermostat language.
- Read the end-user license agreement and accept it.
- Answer whether the homeowner has a Lennox Account. Yes leads to pairing in the Lennox Home app; No leads to creating an account.
Applies to: Lennox L40 smart thermostat, post-setup customization
Source: Home (L40) User Guide, p. 5-6. Written in our own words; check the manual for your exact model.
Initial setup walkthrough after installation
General · L40
The thermostat walks the user through first-time setup after a technician has installed it. Dealer ID and phone number can be skipped.
- Pick the language, then select the L40 Thermostat setup route.
- Enter the dealer ID and dealer phone number, or skip both.
- Set the country, time zone, daylight savings, date and time.
- Choose °F or °C for the temperature unit.
- Select the indoor unit type and the outdoor unit type.
- Check the outdoor unit capacity. Default is 36.0 kBTU; adjust with − or + if needed.
- Set the compressor short cycle delay in seconds.
- Set filter reminders for filters 1 and 2, and any maintenance reminders.
- Finish setup. The Congratulations screen confirms it is complete.
Applies to: Lennox L40 smart thermostat, first-time setup after installation
Source: Home (L40) User Guide, p. 4-5. Written in our own words; check the manual for your exact model.
Multiple S40 thermostats in one home
General · S40 Smart Thermostat
Every S40 thermostat in the home must be on the same 2.4 GHz Wi-Fi network or they will not communicate with each other.
- Confirm all S40 thermostats in the home join the same 2.4 GHz network.
- Do not put one thermostat on a 5 GHz-only or different network.
Applies to: Multi-thermostat homes
Source: Lennox S40 Smart Thermostat User Guide, p. 14. Written in our own words; check the manual for your exact model.
Setup Process on the thermostat
General · S40 Smart
The dealer completes part of setup. The homeowner finishes it on the thermostat and in the Lennox Smart Thermostat app. Setup covers language, EULA, Wi-Fi and pairing with the app.
- Press the S40 Setup Pending badge on the home screen, then press Yes.
- Select the language (English, Spanish or French).
- Review the EULA and select I Agree.
- Select the home Wi-Fi network from the list. For a hidden network, see page 15.
- Enter the Wi-Fi password using the virtual keyboard and confirm.
- Wait for the connection confirmation and press OK.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 6. Written in our own words; check the manual for your exact model.
Sleep Mode rules
General · S40 Smart Thermostat
Sleep Mode lets one or more Smart Room Sensors set the room temperature and can turn off the thermostat's own sensor. At least one Smart Room Sensor must be ON, or the current temperature cannot be calculated.
- Confirm at least one Smart Room Sensor is active before setting Sleep Mode.
- Disable Sleep Mode to clear the From and To fields.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 30 and 32. Written in our own words; check the manual for your exact model.
Smart Away requirements
General · S40 Smart Thermostat
Smart Away only works when the phone or tablet app is running and logged in, with Wi-Fi and location enabled. Android needs high accuracy location mode.
- Install and open the Lennox S40 Thermostat app and log into the account.
- Enable Wi-Fi and location services on each participating device.
- On Android, set location mode to high accuracy.
- On the app, go to Menu > Settings > Away, turn ON Smart Away and turn ON participate.
- Set the inner Away Fence (default 2 miles).
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 29. Written in our own words; check the manual for your exact model.
Wi-Fi network requirements for the S40 thermostat
General · S40 Smart Thermostat
The thermostat has limits on network name length, password length and security. A guest network cannot be used. Lennox S40 and S30 thermostats do not talk to each other even on the same network.
- Keep the access point name to 32 characters or fewer, visible or hidden.
- Keep the Wi-Fi password to 63 characters or fewer, with no spaces and no % symbol.
- Turn on Wi-Fi security if the network is open. Supported types are WEP, WPA, WPA2 and WPA3.
- Do not connect to a guest network.
- Connect the thermostat through a secure network located in the same home as the thermostat.
- Do not expect an S30 and an S40 thermostat to communicate with each other.
Applies to: Lennox S40 Smart Thermostat Wi-Fi connection
Source: Lennox S40 Smart Thermostat User Guide, p. 14. Written in our own words; check the manual for your exact model.
Other
Everything else worth knowing at the appliance.
Run the fireplace during a power outage
Gas fireplace · Lennox Elite Linear View LDV42/LDV54
4 AA batteries in the backup holder keep the flame ON/OFF working without 120 V.
- Remove the surround (if fitted) and the door.
- Pull the battery holder out on its cable from the IPI/CPI bracket on the left side.
- Load 4 AA batteries (flat end to the spring), put the holder back, refit the door.
- If the receiver batteries are dead too, slide the receiver to ON to light it by hand.
Applies to: Elite Linear View LDV42N, LDV42P, LDV54N, LDV54P (SIT Proflame DFC control, remote wall receiver)
Source: Lennox Hearth Elite Linear View Direct-Vent Gas Fireplace LDV42/LDV54 Installation Instructions 506011-02 (06/2012), Field Wiring p.25-26. Written in our own words; check the manual for your exact model.
Allergen Defender requirements
General · S40 Smart Thermostat
Allergen Defender runs the fan between heating or cooling calls when pollen is high. Internet weather must be enabled. Best with a MERV 11 or higher filter. Pollen types checked are grass, ragweed, mold, tree and overall pollen.
- Enable Internet weather.
- Go to Menu, Settings, Fan and turn Allergen Defender on.
- Use a MERV 11 or higher filter.
Applies to: Lennox S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 32. Written in our own words; check the manual for your exact model.
Auxiliary heat and balance point
General · S40 Smart Thermostat
Auxiliary heat is a backup heat source used when the heat pump cannot keep up. The balance points set which source runs at each outdoor temperature. Above the high balance point only the heat pump runs. Below the low balance point only auxiliary heat runs. Between the two, both can run.
- Check the high and low balance point settings for the system.
- In dual-fuel systems, the heat pump shuts off and the gas or oil unit provides all heat.
- With an air handler and electric heat, auxiliary heat runs with the heat pump when the load requires it.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 32. Written in our own words; check the manual for your exact model.
Check Wi-Fi RSSI from the thermostat
General · L40 Smart Thermostat
RSSI shows the signal strength of the router as received by the device. A higher (less negative) value is a stronger signal.
- Go to Menu > Settings > Wi-Fi.
- Select the right arrow next to the Wi-Fi network name, then select it again.
- Read the RSSI value on the details screen.
Applies to: Lennox L40 Smart Thermostat
Source: Lennox Home (L40) User Guide, p. 24. Written in our own words; check the manual for your exact model.
Clean the screen
General · S40 Smart Thermostat
The lock screen can be used to clean the display.
- Lock the screen and wipe the display.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 24. Written in our own words; check the manual for your exact model.
Create home record and link thermostat to location
General · L40
Associates the thermostat with the physical home address and sets up the customization options.
- On the Create Home or Select Existing Home screen, tap to add a home.
- Enter the house name, country/region, address, city/state and zip/postal code, then save.
- Tap the notebook/heart icon to continue customization, then tap Yes.
- Choose whether to set a schedule, including day grouping, system mode, fan mode, temperature adjustments and Smooth Set Back.
- Set the heating and cooling temperatures used when One Touch Away is active.
- Choose whether to receive monthly performance reports.
- Choose whether to receive service and maintenance alerts, and whether the local dealer also receives them.
- Choose whether the local dealer may remotely review data and diagnose the system through Advanced Diagnostics.
Applies to: Lennox L40 with Lennox Home app
Source: Home (L40) User Guide, p. 7. Written in our own words; check the manual for your exact model.
Dealer remote access during a service call
General · S40 Smart Thermostat
Dealer support options are set by the homeowner. Advanced diagnostics stays off until the homeowner allows temporary access. Remote sharing and alerts are off by default.
- Ask the homeowner to set Dealer Support Access > Advanced Diagnostics and Troubleshooting to On / Always if remote troubleshooting is needed.
- Or follow the temporary advanced diagnostics access procedure on page 46 of the guide.
- Confirm the homeowner's permission before remote work starts.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 25. Written in our own words; check the manual for your exact model.
Enable Peak Monitoring
General · L40 Smart Thermostat
Peak Monitoring lets the homeowner's utility control the thermostat during peak energy events. Enrollment is a two-step process that starts with the utility.
- Go to Menu > Settings > Peak Monitoring.
- Turn on enable energy savings.
- If it fails, try again in a few minutes.
- Toggle enable Peak Monitoring ON and verify the utility has a Demand Response program.
- Write down the registration code and select OK.
- Select enroll Peak Monitoring, enter the URL from the energy provider and select DONE.
- Confirm enrollment shows enrolled and connection shows connected.
Applies to: Lennox L40 Smart Thermostat
Source: Lennox Home (L40) User Guide, p. 19. Written in our own words; check the manual for your exact model.
Enable Temporary Advanced Diagnostics access
General · L40 Smart Thermostat
When the dealer sends a request, the homeowner accepts it from the notification. The dealer then has 24 hours for remote diagnostics. Access ends automatically after that. The mobile app must allow notifications from Lennox Home.
- Accept the Temporary Advanced Diagnostics request from the notification on the mobile device or thermostat.
- Confirm the Advanced Diagnostics In Progress icon shows on the home screen.
Applies to: Lennox L40 Smart Thermostat
Source: Lennox Home (L40) User Guide, p. 22. Written in our own words; check the manual for your exact model.
End Advanced Diagnostics access
General · L40 Smart Thermostat
Ending access disconnects the dealer. If a diagnostic is running, the disconnect happens after the service is complete.
- Tap the Advanced Diagnostics in progress icon.
- Tap End Access.
- Press Yes on the End Advanced Diagnostics Access dialog.
- Press OK on the Remote Access has been canceled dialog.
Applies to: Lennox L40 Smart Thermostat
Source: Lennox Home (L40) User Guide, p. 22. Written in our own words; check the manual for your exact model.
Filter and service reminder choices
General · L40
The homeowner picks how often filter reminders are sent. Service and maintenance alerts are optional.
- During setup or customization, choose how often filter reminders are sent.
- Choose Yes to receive service or maintenance notifications, or No to opt out.
- If alerts are enabled, choose whether the local Lennox Dealer also receives them.
Applies to: Lennox L40 smart thermostat
Source: Home (L40) User Guide, p. 3, 5, 7. Written in our own words; check the manual for your exact model.
Google Assistant limits in Schedule and Perfect Temp modes
General · S40
Temperature changes by Google Assistant are not supported while a schedule or Perfect Temp is active; the assistant replies with mode not supported. In Heat/Cool mode, changes keep the existing heat and cool set point range. The Google Home app thermostat image shows the approximate center of the two set points.
- Switch to a manual mode before adjusting temperature by voice in Schedule or Perfect Temp.
- Note that adjusting one set point moves the other to keep the same range.
Applies to: Lennox S40 Smart Thermostat with Google Assistant
Source: Lennox S40 Smart Thermostat User Guide, p. 43. Written in our own words; check the manual for your exact model.
Home screen status icons
General · L40
Animated and static icons show what the system is doing. Use them to check operating status before service calls.
- A menu icon with a number shows how many active notifications exist.
- A heating or cooling animation above the system name means the home is being heated or cooled.
- A fan icon shows whether the fan is On (continuous), Auto (follows schedule), or Circulate (cycles during inactivity).
Applies to: L40 Smart Thermostat home screen
Source: L40 User Guide (English), p. 16. Written in our own words; check the manual for your exact model.
Lennox Home app home screen
General · L40
The app mirrors the thermostat home screen and adds the home name, system name, and local weather based on the account zip code. Tapping Status shows humidity, fan operation, active schedules and ventilation.
- Check the home name and system name at the top.
- Tap Status to see humidity, fan operation, schedules and ventilation.
- Tap the thermostat or zone view button to return to the thermostat home screen.
Applies to: Lennox Home app
Source: L40 User Guide (English), p. 10. Written in our own words; check the manual for your exact model.
Operating mode choices
General · S40 Smart Thermostat
The Mode screen sets how the system runs. Available options are listed below.
- Go to Menu > System > Mode.
- Pick Emerg Heat, Heat Only, Heat / Cool, Cool Only or Off.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 25. Written in our own words; check the manual for your exact model.
Pair the thermostat with Lennox Home and join Wi-Fi
General · L40
Links the thermostat to the Lennox Home app and connects it to the home network.
- In the Lennox Home app, open the menu and select Add Smart Thermostat.
- Select L40 and follow the on-screen pairing instructions.
- Tap OK after the pairing confirmation.
- Select the home Wi-Fi network from the Available Networks list.
- Enter the Wi-Fi password. The Show Password box can be ticked to check it.
- If the network does not show in the list, use the hidden access point instructions on page 23.
Applies to: Lennox L40 with Lennox Home app
Source: Home (L40) User Guide, p. 6. Written in our own words; check the manual for your exact model.
Perfect Temp limits
General · S40 Smart Thermostat
Perfect Temp is available only on non-zoning systems. It uses one set point for heating and cooling and is OFF by default. The Heat and Cool indicator colors and order are reversed, and the mode shows Auto. Google Assistant cannot adjust the temperature while Perfect Temp is on.
- Go to Menu, Settings, Fan or Heat/Cool and turn Perfect Temp on only on non-zoning systems.
Applies to: Lennox S40 non-zoning systems
Source: Lennox S40 Smart Thermostat User Guide, p. 32. Written in our own words; check the manual for your exact model.
Postpone air cleaning from the thermostat
General · S40
When poor air quality triggers cleaning, the Home screen shows a Cleaning Air notice. The homeowner can view details or postpone the cleaning for a set time.
- Select Cleaning Air on the thermostat Home screen.
- Choose Postpone and pick 1, 2, 4, 8 or 24 hours.
- Choose View Details to see the air quality details instead.
Applies to: Lennox S40 Smart Thermostat with Smart Air Quality Monitor
Source: Lennox S40 Smart Thermostat User Guide, p. 42. Written in our own words; check the manual for your exact model.
Rename the system for voice control
General · S40 Smart Thermostat
The name System makes voice commands from smart home devices harder to use. Renaming the system avoids this.
- Go to Menu > Settings > System Info and rename the system.
- Avoid the name System or system if voice control will be used.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 25. Written in our own words; check the manual for your exact model.
Requirements to enable Smart Away
General · L40 Smart Thermostat
Smart Away needs both Home Info and Account completed first. The phone or tablet must run Lennox Home, be logged in, and have Wi-Fi and location enabled.
- Complete Home Info and Account in the app.
- Keep Lennox Home running and logged in on the mobile device.
- Enable Wi-Fi and location on the mobile device. Android devices need location mode set to high accuracy.
- Go to Menu > Settings > Away and turn Smart Away ON, then turn participate ON.
Applies to: Lennox L40 Smart Thermostat with Lennox Home app
Source: Lennox Home (L40) User Guide, p. 18. Written in our own words; check the manual for your exact model.
Schedule profile types
General · S40 Smart Thermostat
Each schedule profile below has a different purpose. Summer, Spring/Fall and Winter give average set points, and Save Energy uses EPA Energy Star values. No Schedule means every change is manual.
- Pick the profile in Menu > System > Schedule.
- Edit the time periods and set points as needed.
- Use the schedule options at the top right to rename, assign days, set system and fan mode, or restore defaults.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 26. Written in our own words; check the manual for your exact model.
Setup Pending badge
General · S40 Smart
If setup is skipped, a S40 Pending Setup badge stays on the home screen until the homeowner clears it.
- Press the Setup Pending badge to resume setup.
- Complete the Setup Process to clear the badge.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 6. Written in our own words; check the manual for your exact model.
Smart Air Quality Monitor response by equipment
General · S40 Smart Thermostat
With no IAQ equipment the blower runs to circulate air. With a high efficiency filter the blower runs through the filter. With Pure Air the system runs Pure Air. With an ERV or HRV, outdoor air is brought in only if it is better than indoor air; otherwise the indoor blower runs.
- Confirm the IAQ equipment installed so the thermostat uses the correct method.
- Note the thermostat only starts showing monitor data after the first blower, cooling or heating call.
Applies to: Lennox Smart Air Quality Monitor
Source: Lennox S40 Smart Thermostat User Guide, p. 40. Written in our own words; check the manual for your exact model.
Smart Air Quality Monitor side switch function
General · S40
The side switch is mainly there to turn off the internal fan when the monitor is in a bedroom. UP turns on the fan and sends air quality data. DOWN turns the fan off and stops the data, and the thermostat keeps showing the last reading.
- Set the side switch to UP to run the fan and send data.
- Set the side switch to DOWN to turn off the fan and stop data.
Applies to: Lennox Smart Air Quality Monitor
Source: Lennox S40 Smart Thermostat User Guide, p. 40. Written in our own words; check the manual for your exact model.
Smart Away occupancy-based energy saving
General · L40
Smart Away uses occupants' smartphone GPS to detect when the house is empty. It sets back the temperature to save energy when nobody is home, and returns the system to normal when someone is on the way home.
Applies to: Lennox L40 smart thermostat with occupant smartphones
Source: Home (L40) User Guide, p. 3. Written in our own words; check the manual for your exact model.
Smart Room Sensor excluded from averaging
General · S40 Smart Thermostat
By default a sensor is excluded from temperature averaging if its reading differs from the thermostat by more than 7°F. The message 'Device is not participating as temperature readings are abnormally high/low' appears on the sensor detail screen.
- Check that the sensor is not in direct sunlight, near a discharge vent, or in unconditioned space.
- If the location is suitable and the sensor still disagrees with the actual room temperature, replace the sensor.
Applies to: Lennox Smart Room Sensor
Source: Lennox S40 Smart Thermostat User Guide, p. 39. Written in our own words; check the manual for your exact model.
Thermostat home screen layout (L40)
General · L40
Where the main controls and status icons sit on the thermostat home screen. Animated icons show active heating, cooling, fan and ventilation calls, and separately show configuration, maintenance, Wi-Fi, peak monitoring and upcoming-function notices.
- Use the Menu button to reach notifications and general information.
- Use the manual setting button to put the system into a preset set point.
- Drag the heating or cooling adjustment tool to change the set point.
- Read the actual room temperature marker and current room temperature.
- Check the upper icon area for active calls or notices.
Applies to: L40 Smart Thermostat display
Source: L40 User Guide (English), p. 9. Written in our own words; check the manual for your exact model.
Third-party voice control limits (Amazon Alexa)
General · S40
Alexa commands fail when the thermostat is in Away or Smart Away. Heat/Cool mode uses a midpoint: a request for 70 degrees sets heat to 69 and cool to 72. Only one home can be paired with Alexa. The thermostat must be online and the user logged in to the Lennox account.
- Keep the thermostat connected to the Internet and the user logged in to the Lennox account.
- Do not expect temperature changes by voice while in Away or Smart Away.
- Rename the system from System or Thermostat to avoid voice command conflicts during setup.
Applies to: Lennox S40 Smart Thermostat with Amazon Alexa
Source: Lennox S40 Smart Thermostat User Guide, p. 42-43. Written in our own words; check the manual for your exact model.
Unique schedules for each zone
General · S40 Smart Thermostat
In a zoned system, a schedule profile changes for every zone that uses it. Renaming the profiles gives each zone its own schedule. No Schedule and Schedule IQ cannot be renamed.
- Rename Summer, Spring/Fall, Winter and Save Energy to the zone name, such as Bedroom or Kitchen.
- Assign each renamed profile to its matching zone.
Applies to: S40 Smart Thermostat
Source: Lennox S40 Smart Thermostat User Guide, p. 27. Written in our own words; check the manual for your exact model.
Using Away mode
General · L40
Away is turned on or off from the green leaf icon. While Away, the Away set points control the high and low temperature range.
- Tap the Away icon near the bottom of the home screen to toggle it on or off.
- Check the Away icon at the upper right in the app or lower left on the thermostat.
- To change the Away range, tap Heat to or Cool to and slide the adjustment tool.
- Tap Cancel at the bottom of the home screen to end Away.
Applies to: L40 Smart Thermostat and Lennox Home app
Source: L40 User Guide (English), p. 13. Written in our own words; check the manual for your exact model.
Related
Same tips in your pocket
The HVACopedia app has these tips, every error code and the settings tables offline.
For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.