Lennox · Furnace · Ignition

Two-stage furnace ignition retries and watchguard

EL296UHVSL280UHVSL280UHNVSL297UHNV

What happens, in order

  1. Warm-up ends and the gas valve opens for the 4 second trial
  2. No flame in 4 seconds control does a 35 second inter-purge and warm-up, then tries again
  3. Five trials in total, then watchguard flame failure mode
  4. After 60 minutes the control restarts the ignition sequence
  5. The built-in watchguard also breaks and remakes the thermostat demand after one hour of continuous demand to reset an ignition lockout
  6. Soft lockouts for too many retries or recycles clear when a later heat call finishes successfully

Timings and thresholds

ItemValue
Trials for ignition5 total
Inter-purge and warm-up between trials35 s
Watchguard reset60 min

Codes you may see during this

E270 E271 E272 E273 E274 E275 E290

Applies to: Two-stage variable-speed Lennox furnaces

Models

EL296UHVSL280UHVSL280UHNVSL297UHNV

More Lennox furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Lennox SL280UHV installation manual 508245-01 (04-2024), Heating Sequence of Operation p.46; Lennox SL280UHNV service manual Corp 1601-L8 (rev 04-2024), Sequence of Operation; Lennox SL297UHNV installation manual 507760-02 (02-2018), Heating Sequence of Operation pp.51-52; Lennox EL296UHV installation manual, Ignition and Two Stage Operation pp.27-28. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.