Lennox · Furnace · Cooling

Cooling call on single-stage furnace blower

EL195UHNEML180UHEK

What happens, in order

  1. Control powers up and passes the self-check; polarity, ground and rollout are monitored the whole time
  2. Thermostat calls for cooling (Y/G)
  3. Compressor contactor and indoor blower are energized after a 2 second delay, blower on cooling speed
  4. The EAC terminal is energized with the blower
  5. Thermostat opens compressor stops, and the blower and EAC stay on for a 45 second off delay
  6. Low voltage, reversed polarity or poor ground are flagged on the LED but the control keeps answering the cooling call

Timings and thresholds

ItemValue
Blower on delay2 s
Blower off delay45 s, not adjustable

Codes you may see during this

EL195 flashes 1 2 8 13 ML180 E110 E111 E112 E117 E200

Applies to: EL195UHNE, ML180UHEK

Models

EL195UHNEML180UHEK

More Lennox furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Lennox EL195UHNE service manual Corp 1801-L1 (rev 04-2024), Sequence of Operation pp.9-10 and 49-54; Lennox ML180UHEK service manual 100166, Heating Ignition Sequence p.11 and Sequence of Operation pp.36-40. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.