Lennox · Furnace

E200 Flame rollout - hard lockout

Critical severity EL296UHVLennox SL280UHVLennox ML180UHELennox SL297NV

What the control is telling you

The rollout switch circuit is open or was previously open; furnace is in hard lockout.

Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)

Likely causes

  • Blocked heat exchanger
  • Blocked flue/vent
  • Lack of combustion air
  • Failed rollout switch

Test and repair steps

  1. Warning: A rollout trip means flame came out of the burner box; find the cause before resetting.
  2. Inspect the heat exchanger, vent and combustion air piping for blockage.
  3. Check burner alignment and burner box cover in place.
  4. Check burner faces and crossovers for blockage and clean (soft brush vacuum) if needed.
  5. After reset, a hard lockout requires a thermostat reset or power cycle.
  6. Rollout switches (S47) are on top of the burner box, one each side; they open at 210°F.
  7. Once the cause is fixed, press the manual reset on the switch, or replace it if it will not reset.
  8. Test furnace operation through a full heat cycle.

Settings for these units

Recommended filter size by cabinet width · EL296UHV

Cabinet widthSide returnBottom return
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is the quantity of filters.

Filters are field supplied and installed outside the furnace; inspect monthly.

Recommended filter size by cabinet width · Lennox SL280UHV

Cabinet widthSide returnBottom return
14-1/2 in.16 x 25 x 1 in. (1)14 x 25 x 1 in. (1)
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is filter quantity; filters are field supplied.

Never run the unit without a filter installed.

Models that show this code

34 models in EL296UHV, Lennox SL280UHV, Lennox ML180UHE, Lennox SL297NV

EL296UH045XV36BEL296UH070XV36BEL296UH090XV36CEL296UH090XV48CEL296UH090XV60CEL296UH110XV48CEL296UH110XV60CEL296UH135XV60DML180UH045E36AKML180UH045XE36AKML180UH070E36AKML180UH070E36BKML180UH070XE36AKML180UH070XE36BKML180UH090E48BKML180UH090E60CKML180UH090XE48BKML180UH110E60CKML180UH110XE60CKML180UH135E60DKSL280UH060NV36ASL280UH070V36ASL280UH080NV48BSL280UH080NV60CSL280UH090V36BSL280UH090V48BSL280UH090V60CSL280UH100NV60CSL280UH110V60CSL280UH135V60DSL297UH040NV36BSL297UH060NV36BSL297UH080NV48CSL297UH080NV60C

Other codes on the same units

  • E161 Refrigerant leak sensor #2 wrong type
  • E163 Furnace control board failure
  • E164 Low GWP test mode active
  • E180 Outdoor air temperature sensor failure
  • E201 Indoor blower communication failure
  • E202 Blower motor mismatch
  • E203 Unit capacity not programmed
  • E204 Gas valve miswired

Sequence of operation

What the unit does around this code, step by step.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.34; Ignition Control 107045-XX Diagnostic Codes table, p.41, Troubleshooting: Heating Sequence of Operation flowchart, p.110-112, Maintenance p.89. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.