Lennox · Furnace · Ignition

Single-stage furnace ignition retries and watchguard

EL195UHNEML180UHEK

What happens, in order

  1. Gas valve opens and the 4 second trial for ignition runs
  2. If flame is not proven in 4 seconds, the gas valve closes and the control does an inter-purge and ignitor warm-up of 35 seconds before the next try
  3. The control makes up to five trials in total, including the first
  4. After five failed trials the control goes into watchguard flame failure mode and shuts the gas valve
  5. After a 60 minute reset period the control starts the ignition sequence again from the beginning
  6. Flame lost after being proven during a call counts as a recycle; too many recycles also put the control in watchguard
  7. Low flame signal is flagged separately (EL195 flash 4) when the sensor current is weak

Timings and thresholds

ItemValue
Trials for ignition5 total
Time between trials35 s inter-purge and warm-up
Watchguard reset60 min

Codes you may see during this

EL195 flashes: 3 burner failed to light or lost flame; 4 low flame signal; 5 watchguard, retries or recycles exceeded. ML180: E270, E271, E272, E273, E274, E275

Applies to: EL195UHNE, ML180UHEK

Models

EL195UHNEML180UHEK

More Lennox furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Lennox EL195UHNE service manual Corp 1801-L1 (rev 04-2024), Sequence of Operation pp.9-10 and 49-54; Lennox ML180UHEK service manual 100166, Heating Ignition Sequence p.11 and Sequence of Operation pp.36-40. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.