Lennox · Furnace · Standby/shutdown

Continuous fan with heat or cool calls

EL195UHNEML180UHEK

What happens, in order

  1. Fan switched to ON at the thermostat the G call runs the blower at fan speed and powers the EAC terminal
  2. If a call for heat arrives, the blower keeps running at fan speed until the 30 second heat delay is over, then goes to heating speed; EAC and HUM stay on
  3. If a call for cooling arrives, the blower moves to cooling speed and EAC stays on
  4. When the call ends, the HUM terminal drops after the inducer post-purge
  5. After the blower off delay the blower returns to fan speed and EAC stays energized

Timings and thresholds

ItemValue
Heat speed switch delay30 s
Inducer post-purge5 s

Applies to: EL195UHNE, ML180UHEK

Models

EL195UHNEML180UHEK

More Lennox furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Lennox EL195UHNE service manual Corp 1801-L1 (rev 04-2024), Sequence of Operation pp.9-10 and 49-54; Lennox ML180UHEK service manual 100166, Heating Ignition Sequence p.11 and Sequence of Operation pp.36-40. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.