Lennox · Furnace

E273 Soft lockout - recycles exceeded, flame failure

High severity EL296UHVLennox SL280UHVLennox ML180UHELennox SL297NV

What the control is telling you

Last recycle was due to loss of flame.

Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)

Likely causes

  • Dirty flame sensor
  • Poor ground
  • Gas supply fluctuation

Test and repair steps

  1. Enter Flame Signal mode hold the diagnostic push button until a solid F shows, release, and read flame current in microamps.
  2. Compare 2.6 uA or more is normal, 2.5 uA or less is low, and the flame drops out at 1.1 uA.
  3. Warning: Turn off power and gas before removing the flame sensor from the left side of the burner support.
  4. Clean the sensor rod (remove oxide) or replace it if damaged or still weak after cleaning.
  5. Measure neutral-to-ground voltage and verify the furnace has a solid earth ground; the control is polarity sensitive.
  6. Check ground at the control AC volts between line neutral and the C terminal should not exceed 2 VAC at idle, 5 VAC with inducer/ignitor on, 10 VAC with blower on; a wide swing under load means a poor ground. Line hot to neutral should be 97-132 VAC.
  7. Check gas pressures with a manometer supply natural gas 4.5-13.0 in. w.c. (LP 11.0-13.0); manifold natural 1.7 low fire / 3.5 high fire (LP 4.5 / 10.0) at 0-4500 ft.
  8. Clean burners if dirty (soft brush vacuum on burner faces) and confirm burners are centered in the burner ports.
  9. Run a heat cycle and confirm stable flame current.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.36; Ignition Control 107045-XX Diagnostic Codes table, p.43, Heating System Service Checks p.82-85, Maintenance p.88-89, Unit Components p.52. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.