Lennox · Furnace

E223 Low pressure switch failed open

High severity EL296UHVLennox SL280UHVLennox ML180UHELennox SL297NV

What the control is telling you

Low-fire pressure switch does not close on a call for heat.

Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)

Likely causes

  • Blocked vent or intake
  • Inducer not running properly
  • Cracked/plugged hose
  • Condensate backup
  • Failed switch

Test and repair steps

  1. Warning: Never jumper or bypass the combustion air pressure switch; it is a safety shutdown device and is not field adjustable.
  2. Know the sequence on a heat call the pressure switches must be open; the low-fire switch must close within 120 s of the inducer starting or the inducer goes to high speed; if low and high switches are not closed within 30 s after that, the inducer shuts off for a 5-minute wait. For second stage, the high-fire switch must close within 10 s or a 5-minute delay follows; after 5 failed attempts the furnace runs low fire for the rest of the call.
  3. Check the vent (exhaust) and combustion air intake piping for blockage, ice, sags holding water, or bad terminations. After snow, ice or freezing fog, check intake and exhaust terminations and remove any obstruction.
  4. Confirm the combustion air inducer starts and runs correctly on both low and high speed; listen for bearing noise.
  5. Inspect the pressure switch hoses for cracks, kinks, water, or loose fittings, and confirm they are on the correct ports.
  6. Check the condensate trap and the condensate hose screens at the cold end header box for blockage (power off; twist and pull screens, rinse); prime the trap with 10 fl. oz. (300 ml) of water if dry. If furnace and coil drains are combined, the A/C drain must be vented or the pressure switch will not work properly.
  7. Measure the switch differential with a manometer: tee into the positive and negative sides at the switch, read at start-up and again after about 5 minutes of steady run.
  8. Compare readings to the set-point tables at 0-4500 ft the low/high fire break points are e.g. -045: 0.35/0.60 in. w.c., -090: 0.50/0.90, -110 and -135: 0.45/0.90. Close (make) is 0.15 in. w.c. above the break point.
  9. Check pressure switch wiring and connections at the integrated control; replace the switch if the measured differential is adequate but the contacts do not respond.

Settings for these units

Recommended filter size by cabinet width · EL296UHV

Cabinet widthSide returnBottom return
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is the quantity of filters.

Filters are field supplied and installed outside the furnace; inspect monthly.

Recommended filter size by cabinet width · Lennox SL280UHV

Cabinet widthSide returnBottom return
14-1/2 in.16 x 25 x 1 in. (1)14 x 25 x 1 in. (1)
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is filter quantity; filters are field supplied.

Never run the unit without a filter installed.

Models that show this code

34 models in EL296UHV, Lennox SL280UHV, Lennox ML180UHE, Lennox SL297NV

EL296UH045XV36BEL296UH070XV36BEL296UH090XV36CEL296UH090XV48CEL296UH090XV60CEL296UH110XV48CEL296UH110XV60CEL296UH135XV60DML180UH045E36AKML180UH045XE36AKML180UH070E36AKML180UH070E36BKML180UH070XE36AKML180UH070XE36BKML180UH090E48BKML180UH090E60CKML180UH090XE48BKML180UH110E60CKML180UH110XE60CKML180UH135E60DKSL280UH060NV36ASL280UH070V36ASL280UH080NV48BSL280UH080NV60CSL280UH090V36BSL280UH090V48BSL280UH090V60CSL280UH100NV60CSL280UH110V60CSL280UH135V60DSL297UH040NV36BSL297UH060NV36BSL297UH080NV48CSL297UH080NV60C

Other codes on the same units

  • E204 Gas valve miswired
  • E205 Gas valve relay contact shorted
  • E206 Gas valve second-stage relay failure
  • E207 Hot surface ignitor open
  • E224 Low pressure switch failed closed
  • E225 High pressure switch failed open
  • E226 High pressure switch failed closed
  • E227 Low pressure switch opened during ignition or run

Sequence of operation

What the unit does around this code, step by step.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.35; Ignition Control 107045-XX Diagnostic Codes table, p.42, Troubleshooting: Heating Sequence of Operation flowchart, p.110-112, Maintenance p.87. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.