Lennox · Furnace
E227 Low pressure switch opened during ignition or run
What the control is telling you
Low pressure switch opened during trial for ignition or while running.
Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)
Likely causes
- Vent/intake restriction
- Wind or ice at termination
- Inducer problem
- Water in hoses or header box
Test and repair steps
- Warning: Never jumper or bypass the combustion air pressure switch; it is a safety shutdown device and is not field adjustable.
- Know the sequence on a heat call the pressure switches must be open; the low-fire switch must close within 120 s of the inducer starting or the inducer goes to high speed; if low and high switches are not closed within 30 s after that, the inducer shuts off for a 5-minute wait. For second stage, the high-fire switch must close within 10 s or a 5-minute delay follows; after 5 failed attempts the furnace runs low fire for the rest of the call.
- Check the vent (exhaust) and combustion air intake piping for blockage, ice, sags holding water, or bad terminations. After snow, ice or freezing fog, check intake and exhaust terminations and remove any obstruction.
- Confirm the combustion air inducer starts and runs correctly on both low and high speed; listen for bearing noise.
- Inspect the pressure switch hoses for cracks, kinks, water, or loose fittings, and confirm they are on the correct ports.
- Check the condensate trap and the condensate hose screens at the cold end header box for blockage (power off; twist and pull screens, rinse); prime the trap with 10 fl. oz. (300 ml) of water if dry. If furnace and coil drains are combined, the A/C drain must be vented or the pressure switch will not work properly.
- Measure the switch differential with a manometer: tee into the positive and negative sides at the switch, read at start-up and again after about 5 minutes of steady run.
- Compare readings to the set-point tables at 0-4500 ft the low/high fire break points are e.g. -045: 0.35/0.60 in. w.c., -090: 0.50/0.90, -110 and -135: 0.45/0.90. Close (make) is 0.15 in. w.c. above the break point.
- Check pressure switch wiring and connections at the integrated control; replace the switch if the measured differential is adequate but the contacts do not respond.
Settings for these units
Recommended filter size by cabinet width · EL296UHV
| Cabinet width | Side return | Bottom return |
|---|---|---|
| 17-1/2 in. | 16 x 25 x 1 in. (1) | 16 x 25 x 1 in. (1) |
| 21 in. | 16 x 25 x 1 in. (1) | 20 x 25 x 1 in. (1) |
| 24-1/2 in. | 16 x 25 x 1 in. (2) | 24 x 25 x 1 in. (1) |
Number in brackets is the quantity of filters.
Filters are field supplied and installed outside the furnace; inspect monthly.
Recommended filter size by cabinet width · Lennox SL280UHV
| Cabinet width | Side return | Bottom return |
|---|---|---|
| 14-1/2 in. | 16 x 25 x 1 in. (1) | 14 x 25 x 1 in. (1) |
| 17-1/2 in. | 16 x 25 x 1 in. (1) | 16 x 25 x 1 in. (1) |
| 21 in. | 16 x 25 x 1 in. (1) | 20 x 25 x 1 in. (1) |
| 24-1/2 in. | 16 x 25 x 1 in. (2) | 24 x 25 x 1 in. (1) |
Number in brackets is filter quantity; filters are field supplied.
Never run the unit without a filter installed.
- Filter sizes by cabinet width · Lennox ML180UHE
- Filter sizes by cabinet width · Lennox SL297NV
Models that show this code
34 models in EL296UHV, Lennox SL280UHV, Lennox ML180UHE, Lennox SL297NV
Other codes on the same units
Sequence of operation
What the unit does around this code, step by step.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.35; Ignition Control 107045-XX Diagnostic Codes table, p.42, Troubleshooting: Heating Sequence of Operation flowchart, p.110-112, Maintenance p.87. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.