Lennox · Furnace
E241 Flame sensed out of sequence - flame present
What the control is telling you
Flame is sensed when the gas valve should be closed.
Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)
Likely causes
- Gas valve leaking through or stuck open
Test and repair steps
- Warning: Shut off gas to the furnace (gas valve switch OFF, by hand only - never use tools; replace the valve if the switch will not move).
- With no call for heat, confirm whether flame is present or flame current is still being sensed.
- Check if the gas valve is being energized without demand (shorted wiring or control relay).
- If the valve leaks through while de-energized, replace it with the same type of valve; do not attempt repair.
- After repair, restore gas, leak-check connections with a gas leak detector (no open flame) and run a full heat cycle.
- Code clears once the fault is gone / flame is proven stable.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox ML180UHE
- Filter sizes by cabinet width · Lennox SL297NV
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.35; Ignition Control 107045-XX Diagnostic Codes table, p.42, Start-Up / Gas Valve Operation p.81. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.