Lennox · Furnace
E347 No 24 V on Y1 output
What the control is telling you
With a non-communicating outdoor unit, Y1 relay/stage 1 failed. Operation stopped; critical alert.
Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)
Likely causes
- Y1 pilot relay contacts did not close
- Relay coil not energized
Test and repair steps
- Measure 24 VAC at the Y1 output during a cooling call.
- Check wiring to the outdoor unit.
- Replace the integrated control if no output.
- Clears after reset and Y1 input is sensed.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox SL297NV
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.37; Ignition Control 107045-XX Diagnostic Codes table, p.44. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.