Lennox · Furnace

E106 Twin communication fault

Medium severity Lennox ML180UHE

What the control is telling you

Twinned furnaces have lost their twinning link. Usually one furnace has lost power, or the 24 VAC supplies of the two furnaces are out of phase.

Applies to: ML180UHEK (R-454B era) single-stage 80% furnaces with integrated control 107792-XX (ML180UH045/070/090/110/135, incl. low-NOx X models)

Likely causes

  • Power off at one of the two twinned furnaces
  • 24 VAC secondaries of the two furnaces not in phase
  • Bad or loose wires on C, O and TWIN between the two controls

Test and repair steps

  1. Confirm both twinned furnaces have 120 V power and their doors/interlocks are closed.
  2. Check the twinning wires C, O and TWIN terminals must be connected between the two controls; all thermostat wires go to one control only.
  3. Measure 24 VAC across the R terminals of both furnaces with the transformers in phase; a reading near 48 V means they are out of phase - reverse the primary or secondary leads on one transformer.
  4. On the furnace without thermostat wires, the W call must come from a field-supplied 24 VAC isolation relay (coil W to common, contacts R to W) so its rollout switch cannot be bypassed by the other furnace.
  5. Restore power to both units together and confirm the code clears.

Settings for these units

Filter sizes by cabinet width · Lennox ML180UHE

CabinetSide returnBottom return
A - 14-1/2 in.16 x 25 x 1 (1)14 x 25 x 1 (1)
B - 17-1/2 in.16 x 25 x 1 (1)16 x 25 x 1 (1)
C - 21 in.16 x 25 x 1 (1)20 x 25 x 1 (1)
D - 24-1/2 in.16 x 25 x 1 (2)24 x 25 x 1 (1)

Filters are field supplied; check monthly.

Cabinet letter is the letter after the cooling size in the model number: A = 045E36AK, 070E36AK; B = 070E36BK, 090E48BK; C = 090E60CK, 110E60CK; D = 135E60DK.

Models that show this code

12 models in Lennox ML180UHE

ML180UH045E36AKML180UH045XE36AKML180UH070E36AKML180UH070E36BKML180UH070XE36AKML180UH070XE36BKML180UH090E48BKML180UH090E60CKML180UH090XE48BKML180UH110E60CKML180UH110XE60CKML180UH135E60DK

Other codes on the same units

  • C1 Cooling, stage 1
  • C2 Cooling, stage 2
  • E000 No error in memory
  • E110 Low line voltage
  • E111 Line voltage polarity reversed
  • E112 Ground not detected
  • E113 High line voltage
  • E114 Line frequency out of range

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox ML180UHEK Unit Information 100161/100166, Table 6 Integrated Diagnostic Codes, p.13; Twinning, p.8. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.