E105 Device communication problem

High severity EL296UHVLennox SL280UHVLennox SL297NV

What the control is telling you

No other devices detected on the RSBus; many message errors, usually from electrical noise.

Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)

Likely causes

  • Electrical noise on the RSBus
  • High-voltage wiring run next to communication wiring
  • Miswired or loose connections between thermostat, indoor and outdoor units

Test and repair steps

  1. Check all RSBus wiring between thermostat, indoor unit and outdoor unit for miswiring or loose terminals.
  2. Separate high-voltage wiring from the RSBus communication wiring.
  3. Look for a nearby high-voltage noise source and relocate wiring away from it.
  4. Cycle power and confirm the code clears once communication is restored.

Settings for these units

Recommended filter size by cabinet width · EL296UHV

Cabinet widthSide returnBottom return
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is the quantity of filters.

Filters are field supplied and installed outside the furnace; inspect monthly.

Recommended filter size by cabinet width · Lennox SL280UHV

Cabinet widthSide returnBottom return
14-1/2 in.16 x 25 x 1 in. (1)14 x 25 x 1 in. (1)
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is filter quantity; filters are field supplied.

Never run the unit without a filter installed.

Models that show this code

22 models in EL296UHV, Lennox SL280UHV, Lennox SL297NV

EL296UH045XV36BEL296UH070XV36BEL296UH090XV36CEL296UH090XV48CEL296UH090XV60CEL296UH110XV48CEL296UH110XV60CEL296UH135XV60DSL280UH060NV36ASL280UH070V36ASL280UH080NV48BSL280UH080NV60CSL280UH090V36BSL280UH090V48BSL280UH090V60CSL280UH100NV60CSL280UH110V60CSL280UH135V60DSL297UH040NV36BSL297UH060NV36BSL297UH080NV48CSL297UH080NV60C

Other codes on the same units

  • C1 Cooling, stage 1
  • C2 Cooling, stage 2
  • E000 No error in memory
  • E110 Low line voltage
  • E111 Line voltage polarity reversed
  • E112 Ground not detected
  • E113 High line voltage
  • E114 Line frequency out of range

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.33; Ignition Control 107045-XX Diagnostic Codes table, p.40. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.