Lennox · Furnace

LED1 SLOW flash / LED2 FAST flash Low flame signal

Medium severity Lennox G43UF

What the control is telling you

Flame is proven but the signal is weak. Trips below 0.18 microamps on board 32M88, and below 1.5 microamps on boards 78M47 and 100973-01. The furnace still runs. Low flame current is rated at 0.16-0.17 microamps (32M88) or 0.5-1.4 microamps (78M47, 100973-01).

Applies to: G43UF-24B-045 through G43UF-60D-135 (SureLight boards 32M88, 78M47, 100973-01)

Likely causes

  • Flame sensor rod positioned wrong on the burner
  • Flame sensor rod dirty or coated

Test and repair steps

  1. Turn off power at the disconnect before touching wiring or components.
  2. Check that the sensor rod sits correctly in the flame. Reposition it, or replace it if it cannot be positioned.
  3. Clean the rod with steel wool. Do not use sandpaper. Replace the sensor if cleaning does not help.

Settings for these units

Models that show this code

10 models in Lennox G43UF

G43UF-24B-045G43UF-24B-070G43UF-36B-070G43UF-36C-090G43UF-36C-090HG43UF-48C-090G43UF-48C-110G43UF-48C-110HG43UF-60C-110G43UF-60D-135

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox G43UF Unit Information Corp. 0416-L4, Troubleshooting Chart Problem 6 p.55 and Table 4 p.11. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.