Lennox · Furnace
LED1 OFF / LED2 ON Control board failure or control wired incorrectly
What the control is telling you
Table 4 groups three LED patterns (on/on, on/off, off/on) under one meaning: the board has failed or something is wired wrong to it. Code listed only; the chart gives no further steps.
Applies to: G43UF-24B-045 through G43UF-60D-135 (SureLight boards 32M88, 78M47, 100973-01)
Likely causes
- Failed ignition control board
- Incorrect wiring at the control
Test and repair steps
- Turn off power at the disconnect before touching wiring or components.
- Check the wiring to the control against the wiring diagram.
- If the wiring is correct, replace the control board.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox ML180UHE
- Filter sizes (filter rack kits) · Lennox EL195UHNE
- Filter sizes by cabinet width · Lennox SL297NV
Models that show this code
10 models in Lennox G43UF
Other codes on the same units
- LED1 & LED2 simultaneous FAST flash Normal - heat call in progress
- LED1 & LED2 simultaneous SLOW flash Normal - power on, idle, cooling or continuous fan
- LED1 FAST flash / LED2 SLOW flash 120 V line and neutral reversed
- LED1 OFF / LED2 OFF No power to the control
- LED1 OFF / LED2 SLOW flash Prove switch (pressure switch) open
- LED1 ON / LED2 OFF Control board failure or control wired incorrectly
- LED1 ON / LED2 ON Control board failure or control wired incorrectly
- LED1 ON / LED2 SLOW flash Rollout switch open
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox G43UF Unit Information Corp. 0416-L4 (rev 2-2006), Table 4 Diagnostic Codes p.11. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.