Lennox · Furnace
LED1 OFF / LED2 SLOW flash Prove switch (pressure switch) open
What the control is telling you
The prove switch is not closing with the combustion air inducer running, or it is closed before the inducer starts. Covers blocked intake or exhaust vent too. Shows up as no heat, or burners lighting then shutting off early.
Applies to: G43UF-24B-045 through G43UF-60D-135 (SureLight boards 32M88, 78M47, 100973-01)
Likely causes
- Prove switch stuck closed before the inducer starts
- Inducer wiring wrong or loose, or inducer failed
- Prove switch tubing routed wrong, pinched, broken, blocked or holding condensate
- Low pressure differential from restricted intake or exhaust vent or wrong vent size or length
- Wrong concentric vent kit
- Condensate drain not flowing freely
- Wrong or out-of-calibration prove switch, or failed switch
Test and repair steps
- Turn off power at the disconnect before touching wiring or components.
- With the inducer off, confirm the prove switch is open. Replace it if it is stuck closed.
- If the inducer does not start, check wiring and look for 120 V at the inducer. Replace the inducer if it has power and will not run.
- Check the switch tubing for correct routing, leaks, obstructions and condensate.
- Check the pressure differential across the switch. It should be above the set point printed on the switch.
- Check the intake and exhaust for blockage, and check vent sizing and length against the installation instructions. Confirm the right termination kit is installed.
- Check the condensate line for slope and blockage. It must drain freely while the furnace runs.
- Make sure the correct prove switch is installed. Replace it if nothing else is found.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox ML180UHE
- Filter sizes (filter rack kits) · Lennox EL195UHNE
- Filter sizes by cabinet width · Lennox SL297NV
Models that show this code
10 models in Lennox G43UF
Other codes on the same units
- LED1 & LED2 simultaneous SLOW flash Normal - power on, idle, cooling or continuous fan
- LED1 FAST flash / LED2 SLOW flash 120 V line and neutral reversed
- LED1 OFF / LED2 OFF No power to the control
- LED1 OFF / LED2 ON Control board failure or control wired incorrectly
- LED1 ON / LED2 OFF Control board failure or control wired incorrectly
- LED1 ON / LED2 ON Control board failure or control wired incorrectly
- LED1 ON / LED2 SLOW flash Rollout switch open
- LED1 SLOW flash / LED2 FAST flash Low flame signal
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox G43UF Unit Information Corp. 0416-L4, Troubleshooting Chart Problems 2.2, 2.3, 3.1, 5.1 pp.51-53 and Table 4 p.11. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.