Lennox · Furnace

LED1 SLOW flash / LED2 ON Primary or secondary limit open

High severity Lennox G43UF

What the control is telling you

The control sees an open limit circuit. The inducer will not start on a heat call, but cooling and continuous fan still work. If the limit does not close within 3 minutes the control goes into a 1-hour watchguard lockout.

Applies to: G43UF-24B-045 through G43UF-60D-135 (SureLight boards 32M88, 78M47, 100973-01)

Likely causes

  • Furnace overheated (restricted airflow, dirty filter, blocked supply or return)
  • Primary or secondary limit switch open or failed
  • Loose or wrong wiring at the limit switch(es)

Test and repair steps

  1. Turn off power at the disconnect before touching wiring or components.
  2. Check continuity across the limit switch(es). They reset on their own once cool.
  3. Look for restrictions on the blower inlet (including the filter) and on the outlet air.
  4. Find out why the limit tripped before putting the furnace back in service.
  5. Check limit wiring for miswiring or loose terminals.

Settings for these units

Models that show this code

10 models in Lennox G43UF

G43UF-24B-045G43UF-24B-070G43UF-36B-070G43UF-36C-090G43UF-36C-090HG43UF-48C-090G43UF-48C-110G43UF-48C-110HG43UF-60C-110G43UF-60D-135

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox G43UF Unit Information Corp. 0416-L4, Troubleshooting Chart Problem 2.1 p.51 and Table 4 p.11. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.