Lennox · Furnace
Red LED off No power to control or board fault
What the control is telling you
Red LED is dark: the control has no power or has detected a board fault.
Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)
Likely causes
- No 120 V supply (breaker, switch, door interlock open)
- Tripped 3 A 24 V circuit breaker CB8
- Failed transformer T1
- Failed integrated control
Test and repair steps
- Check the blower door is on (door interlock S51 is in series with line voltage).
- Check breaker/disconnect and 120 VAC at the control LINE and NEUTRAL terminals.
- Check and reset circuit breaker CB8 (3 A at 32 V) in the control box; if it trips again look for a 24 V short.
- Check 24 VAC output of the 40 VA transformer.
- If power is present and the LED stays off, replace the control.
Settings for these units
Filter sizes (filter rack kits) · Lennox EL195UHNE
| Cabinet | Horizontal end rack | Side return rack |
|---|---|---|
| B width (040, 060) | 18 x 25 x 1 (kit 87L96) | 16 x 25 x 1 (kit 44J22) |
| C width (080, 100) | 20 x 25 x 1 (kit 87L97) | 16 x 25 x 1 (kit 44J22) |
Filters are field supplied; check monthly.
100NE60C over 1800 cfm with single side return needs a 20 x 25 x 1 filter via return air base and transition.
Models that show this code
4 models in Lennox EL195UHNE
Other codes on the same units
- 10 flashes Watchguard - pressure switch opened 5 times in one heat demand
- 11 flashes Pressure switch stuck closed before inducer starts
- 12 flashes Flame sensed with gas valve off
- 13 flashes Low line voltage
- Red LED fast flash (heartbeat) Call for heat - burner operation
- Red LED on steady Board fault detected (107163-01)
- Red LED recall button Error recall button on the ignition control
- Red LED slow flash (heartbeat) Normal - idle, continuous fan or cooling
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.