Weil-McLain heat pump error codes
49 codes with causes and test steps.
| Code | Meaning | Severity / type |
|---|---|---|
| C7 | Inverter heat sink too hot | High |
| E0 | Water flow fault (E8 three times) | Critical |
| E2 | Communication fault between wired controller and indoor unit | Medium |
| E5 | Outdoor coil temperature sensor (T3) fault | Medium |
| E6 | Outdoor air temperature sensor (T4) fault | Medium |
| E7 | Buffer tank temperature sensor (Tbt1) fault | Medium |
| E8 | Water flow fault | High |
| E9 | Compressor suction temperature sensor (Th) fault | Medium |
| F1 | DC bus low voltage | High |
| H0 | Communication fault between indoor and outdoor unit | High |
| H1 | Communication fault between main board and inverter board (outdoor) | High |
| H2 | Refrigerant temperature sensor at plate HX outlet (heating) (T2) fault | Medium |
| H3 | Refrigerant temperature sensor at plate HX inlet (heating) (T2B) fault | Medium |
| H4 | L0/L1 protection happened 3 times in an hour | High |
| H5 | Room temperature sensor (Ta) fault | Low |
| H6 | DC fan motor fault | High |
| H7 | AC supply voltage protection | Medium |
| H8 | Pressure sensor fault | Medium |
| H9 | Zone 2 water temperature sensor (Tw2) fault | Medium |
| L0 | DC compressor inverter module fault | High |
| L1 | DC bus low voltage protection | High |
| L2 | DC bus high voltage protection | High |
| L4 | MCE fault | High |
| L5 | Zero speed protection | High |
| L7 | Phase loss protection | High |
| L8 | Compressor speed changed more than 15 Hz in one second | High |
| L9 | Compressor speed off target by more than 15 Hz | High |
| P0 | Low pressure protection | High |
| P1 | High pressure protection | High |
| P3 | AC current protection | High |
| P4 | Compressor discharge temperature too high | High |
| P5 | Water temperature difference too high (Tw_out - Tw_in) | High |
| P6 | Inverter module protection | High |
| CL | Water pump communication wire fault | Medium |
| EA | Compressor discharge temperature sensor (Tp) fault | Medium |
| EE | Hydro-box PCB EEPROM fault | Medium |
| EL | Communication fault between hydraulic module and MH-kit | Medium |
| Eb | Solar panel temperature sensor (Tsolar) fault | Medium |
| Ed | Water inlet temperature sensor (Tw_in) fault | Medium |
| HA | Water outlet temperature sensor (Tw_out) fault | Medium |
| HE | Communication fault with Ta / room thermostat transfer board | Low |
| HF | Outdoor unit EEPROM fault | Medium |
| HH | H6 fan fault 10 times in 120 minutes | High |
| HP | Low pressure in cooling, 3 times in an hour | High |
| Hb | PP three times and Tw_out under 44.6 F | Critical |
| PP | Tw_out - Tw_in reading not normal | Medium |
| Pb | Anti-freeze mode | Low |
| Pd | Outdoor coil (T3) temperature too high | High |
| bH | PED board fault | High |
Models covered
ECO HP 41ECO HP 48ECO HP 55
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.