Weil-McLain · Heat pump
E2 Communication fault between wired controller and indoor unit
What the control is telling you
The wired controller (user interface) and the indoor unit board are not talking.
Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)
Likely causes
- Controller wire not connected
- Wires in the wrong order
- Electrical noise from big loads nearby
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching any wiring.
- Check the wire between the wired controller and the unit at both ends.
- Check the wire order and correct it.
- Look for strong magnetic fields or heavy electrical gear near the wire. Shield it or reroute it.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.3 Error codes, p.55. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.