Weil-McLain · Heat pump
E9 Compressor suction temperature sensor (Th) fault
What the control is telling you
The control reads a bad signal from the Th sensor (suction line).
Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)
Likely causes
- Th connector loose
- Water in the connector
- Th sensor failed
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching any wiring.
- Find the Th connector and push it fully home.
- Look for water or moisture in the Th connector. Dry it out and seal it with waterproof adhesive.
- If the connector is good and the code stays, replace the Th sensor.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
- E5 Outdoor coil temperature sensor (T3) fault
- E6 Outdoor air temperature sensor (T4) fault
- E7 Buffer tank temperature sensor (Tbt1) fault
- E8 Water flow fault
- F1 DC bus low voltage
- H0 Communication fault between indoor and outdoor unit
- H1 Communication fault between main board and inverter board (outdoor)
- H2 Refrigerant temperature sensor at plate HX outlet (heating) (T2) fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.35. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.