Weil-McLain · Heat pump

H1 Communication fault between main board and inverter board (outdoor)

High severity Weil-McLain ECO HP

What the control is telling you

Inside the outdoor unit, the main control board and the inverter module board are not talking.

Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)

Likely causes

  • No power to the inverter board
  • Wire between inverter board and main board loose or broken
  • Main board or inverter (driver) board failed

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching any wiring.
  2. Inverter board can hold a charge power off and wait before touching it.
  3. Power up and look at the indicator light on the inverter module board.
  4. Light off the inverter board has no power. Reconnect its power supply wire.
  5. Light on check the wire between the inverter board and the main board. Reconnect or replace a loose or broken wire.
  6. Still there replace the main board, then the inverter (driver) board, one at a time.

Models that show this code

3 models in Weil-McLain ECO HP

ECO HP 41ECO HP 48ECO HP 55

Other codes on the same units

  • E8 Water flow fault
  • E9 Compressor suction temperature sensor (Th) fault
  • F1 DC bus low voltage
  • H0 Communication fault between indoor and outdoor unit
  • H2 Refrigerant temperature sensor at plate HX outlet (heating) (T2) fault
  • H3 Refrigerant temperature sensor at plate HX inlet (heating) (T2B) fault
  • H4 L0/L1 protection happened 3 times in an hour
  • H5 Room temperature sensor (Ta) fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.35. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.