Weil-McLain · Heat pump

H0 Communication fault between indoor and outdoor unit

High severity Weil-McLain ECO HP

What the control is telling you

The indoor unit (hydro-box) main board and the outdoor main board (PCB B) are not talking to each other.

Applies to: ECO HP 41/48/55 MBH indoor and outdoor units

Likely causes

  • Communication wire between the units not connected or loose
  • Wires in the wrong order
  • Electrical noise from big loads nearby (elevators, large transformers)

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching any wiring.
  2. Check the communication wire between the outdoor main board (PCB B) and the indoor main board at both ends. Connect any loose or missing wire.
  3. Check the wire order at both ends and correct it.
  4. Look for strong magnetic fields or heavy electrical equipment near the units or the wire. Shield the wire or move the unit away from it.

Models that show this code

3 models in Weil-McLain ECO HP

ECO HP 41ECO HP 48ECO HP 55

Other codes on the same units

  • E7 Buffer tank temperature sensor (Tbt1) fault
  • E8 Water flow fault
  • E9 Compressor suction temperature sensor (Th) fault
  • F1 DC bus low voltage
  • H1 Communication fault between main board and inverter board (outdoor)
  • H2 Refrigerant temperature sensor at plate HX outlet (heating) (T2) fault
  • H3 Refrigerant temperature sensor at plate HX inlet (heating) (T2B) fault
  • H4 L0/L1 protection happened 3 times in an hour

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.35; Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.3 Error codes, p.56. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.