Weil-McLain · Heat pump
H4 L0/L1 protection happened 3 times in an hour
What the control is telling you
The unit shows H4 when L0 and L1 trips add up to three within one hour.
Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)
Likely causes
- Same as L0 and L1 (inverter module fault / DC bus low voltage)
Test and repair steps
- Work through the L0 and L1 checks system pressure, compressor phase resistance, U-V-W and L1-L2-L3 wiring, inverter board.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
- H0 Communication fault between indoor and outdoor unit
- H1 Communication fault between main board and inverter board (outdoor)
- H2 Refrigerant temperature sensor at plate HX outlet (heating) (T2) fault
- H3 Refrigerant temperature sensor at plate HX inlet (heating) (T2B) fault
- H5 Room temperature sensor (Ta) fault
- H6 DC fan motor fault
- H7 AC supply voltage protection
- H8 Pressure sensor fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.35. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.