Weil-McLain · Heat pump

H7 AC supply voltage protection

Medium severity Weil-McLain ECO HP

What the control is telling you

Supply voltage to the outdoor unit is outside the allowed range.

Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)

Likely causes

  • Supply voltage out of range
  • Power switched off and on several times quickly
  • Control board failed

Test and repair steps

  1. Measure the supply voltage and compare it to the rating plate (208/230 V, 60 Hz).
  2. Ask if the power was cycled quickly several times.
  3. Turn the power off for more than 3 minutes, then back on.
  4. If the code stays, replace the PCB.

Models that show this code

3 models in Weil-McLain ECO HP

ECO HP 41ECO HP 48ECO HP 55

Other codes on the same units

  • H3 Refrigerant temperature sensor at plate HX inlet (heating) (T2B) fault
  • H4 L0/L1 protection happened 3 times in an hour
  • H5 Room temperature sensor (Ta) fault
  • H6 DC fan motor fault
  • H8 Pressure sensor fault
  • H9 Zone 2 water temperature sensor (Tw2) fault
  • L0 DC compressor inverter module fault
  • L1 DC bus low voltage protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.36. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.