Weil-McLain · Heat pump

L1 DC bus low voltage protection

High severity Weil-McLain ECO HP

What the control is telling you

The inverter saw low DC bus voltage while driving the compressor.

Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)

Likely causes

  • System pressure problem
  • Compressor winding fault
  • U-V-W leads loose or in the wrong order
  • L1-L2-L3 leads to the filter board loose
  • Inverter board failed

Test and repair steps

  1. R32 (A2L) refrigerant only a tech qualified for flammable refrigerant should open the refrigerant circuit.
  2. Inverter board can hold a charge power off and wait before touching it.
  3. Check system pressures.
  4. Measure compressor winding (phase) resistance.
  5. Check the U, V, W compressor leads between the inverter board and the compressor, and their order.
  6. Check the L1, L2, L3 leads between the inverter board and the filter board.
  7. If all of that is good, check or replace the inverter board.

Models that show this code

3 models in Weil-McLain ECO HP

ECO HP 41ECO HP 48ECO HP 55

Other codes on the same units

  • H7 AC supply voltage protection
  • H8 Pressure sensor fault
  • H9 Zone 2 water temperature sensor (Tw2) fault
  • L0 DC compressor inverter module fault
  • L2 DC bus high voltage protection
  • L4 MCE fault
  • L5 Zero speed protection
  • L7 Phase loss protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.38. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.