Weil-McLain · Heat pump

H3 Refrigerant temperature sensor at plate HX inlet (heating) (T2B) fault

Medium severity Weil-McLain ECO HP

What the control is telling you

The control reads a bad signal from the T2B sensor (plate heat exchanger refrigerant side, inlet in heating).

Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)

Likely causes

  • T2B connector loose
  • Water in the connector
  • T2B sensor failed

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching any wiring.
  2. Measure the T2B sensor resistance and compare to a known-good reading.
  3. Find the T2B connector and push it fully home.
  4. Look for water or moisture in the T2B connector. Dry it out and seal it with waterproof adhesive.
  5. If the connector is good and the code stays, replace the T2B sensor.

Models that show this code

3 models in Weil-McLain ECO HP

ECO HP 41ECO HP 48ECO HP 55

Other codes on the same units

  • F1 DC bus low voltage
  • H0 Communication fault between indoor and outdoor unit
  • H1 Communication fault between main board and inverter board (outdoor)
  • H2 Refrigerant temperature sensor at plate HX outlet (heating) (T2) fault
  • H4 L0/L1 protection happened 3 times in an hour
  • H5 Room temperature sensor (Ta) fault
  • H6 DC fan motor fault
  • H7 AC supply voltage protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.3 Error codes, p.56. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.