Weil-McLain · Heat pump
H2 Refrigerant temperature sensor at plate HX outlet (heating) (T2) fault
What the control is telling you
The control reads a bad signal from the T2 sensor (plate heat exchanger refrigerant side, outlet in heating).
Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)
Likely causes
- T2 connector loose
- Water in the connector
- T2 sensor failed
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching any wiring.
- Measure the T2 sensor resistance and compare to a known-good reading.
- Find the T2 connector and push it fully home.
- Look for water or moisture in the T2 connector. Dry it out and seal it with waterproof adhesive.
- If the connector is good and the code stays, replace the T2 sensor.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
- E9 Compressor suction temperature sensor (Th) fault
- F1 DC bus low voltage
- H0 Communication fault between indoor and outdoor unit
- H1 Communication fault between main board and inverter board (outdoor)
- H3 Refrigerant temperature sensor at plate HX inlet (heating) (T2B) fault
- H4 L0/L1 protection happened 3 times in an hour
- H5 Room temperature sensor (Ta) fault
- H6 DC fan motor fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.3 Error codes, p.56. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.