Weil-McLain · Heat pump
H6 DC fan motor fault
What the control is telling you
The outdoor DC fan motor is not running right.
Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)
Likely causes
- Strong wind blowing into the fan and spinning it backwards
- Fan motor failed
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching any wiring.
- Check if strong wind hits the fan side of the unit. Turn the unit or build a wind shield.
- If wind is not the problem, replace the fan motor.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
- H2 Refrigerant temperature sensor at plate HX outlet (heating) (T2) fault
- H3 Refrigerant temperature sensor at plate HX inlet (heating) (T2B) fault
- H4 L0/L1 protection happened 3 times in an hour
- H5 Room temperature sensor (Ta) fault
- H7 AC supply voltage protection
- H8 Pressure sensor fault
- H9 Zone 2 water temperature sensor (Tw2) fault
- L0 DC compressor inverter module fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.35. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.