E7 Buffer tank temperature sensor (Tbt1) fault
What the control is telling you
The control reads a bad signal from the Tbt1 sensor (balance tank).
Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)
Likely causes
- Tbt1 connector loose
- Water in the connector
- Tbt1 sensor failed
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching any wiring.
- Measure the Tbt1 sensor resistance and compare to a known-good reading.
- Find the Tbt1 connector and push it fully home.
- Look for water or moisture in the Tbt1 connector. Dry it out and seal it with waterproof adhesive.
- If the connector is good and the code stays, replace the Tbt1 sensor.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
- E0 Water flow fault (E8 three times)
- E2 Communication fault between wired controller and indoor unit
- E5 Outdoor coil temperature sensor (T3) fault
- E6 Outdoor air temperature sensor (T4) fault
- E8 Water flow fault
- E9 Compressor suction temperature sensor (Th) fault
- F1 DC bus low voltage
- H0 Communication fault between indoor and outdoor unit
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.3 Error codes, p.57. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.