Weil-McLain · Heat pump

E0 Water flow fault (E8 three times)

Critical severity Weil-McLain ECO HP

What the control is telling you

E8 (water flow fault) happened three times, so the unit locks out with E0.

Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)

Likely causes

  • Flow switch wiring shorted or open
  • Water flow too low
  • Flow switch stuck open or closed
  • No power to the circulator, or circulator not running

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching any wiring.
  2. Check the flow switch wiring and reconnect it properly.
  3. Check that the circulator has power and is running.
  4. Do the E8 water flow checks.
  5. If the flow switch stays open or closed all the time, replace it.
  6. Winter fix E0 right away. Left alone, the pump and piping can freeze.

Models that show this code

3 models in Weil-McLain ECO HP

ECO HP 41ECO HP 48ECO HP 55

Other codes on the same units

  • C7 Inverter heat sink too hot
  • E2 Communication fault between wired controller and indoor unit
  • E5 Outdoor coil temperature sensor (T3) fault
  • E6 Outdoor air temperature sensor (T4) fault
  • E7 Buffer tank temperature sensor (Tbt1) fault
  • E8 Water flow fault
  • E9 Compressor suction temperature sensor (Th) fault
  • F1 DC bus low voltage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.3 Error codes, p.55. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.