Weil-McLain · Heat pump
E5 Outdoor coil temperature sensor (T3) fault
What the control is telling you
The control reads a bad signal from the T3 sensor (outdoor heat exchanger).
Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)
Likely causes
- T3 connector loose
- Water in the connector
- T3 sensor failed
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching any wiring.
- Find the T3 connector and push it fully home.
- Look for water or moisture in the T3 connector. Dry it out and seal it with waterproof adhesive.
- If the connector is good and the code stays, replace the T3 sensor.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
- C7 Inverter heat sink too hot
- E0 Water flow fault (E8 three times)
- E2 Communication fault between wired controller and indoor unit
- E6 Outdoor air temperature sensor (T4) fault
- E7 Buffer tank temperature sensor (Tbt1) fault
- E8 Water flow fault
- E9 Compressor suction temperature sensor (Th) fault
- F1 DC bus low voltage
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.34. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.