C7 Inverter heat sink too hot

High severity Weil-McLain ECO HP

What the control is telling you

The heat sink on the inverter module is overheating, so the unit protects itself.

Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)

Likely causes

  • Supply voltage too low
  • Units installed too close together, poor air flow
  • Dirty or blocked outdoor coil
  • Fan or fan motor not running
  • Low water flow, air in the water loop, or pump too small
  • Water outlet temperature sensor loose or failed

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching any wiring.
  2. Check supply voltage. Bring it back into the rated range.
  3. Check spacing around the outdoor unit. Give it more room if it is crowded.
  4. Clean the outdoor coil and clear anything blocking it.
  5. Check that the fan turns. Replace a broken fan blade or fan motor.
  6. Check water flow purge air from the loop and confirm the pump has enough head for the system.
  7. Check the water outlet sensor connector. Reconnect it, or replace the sensor if it is bad.

Models that show this code

3 models in Weil-McLain ECO HP

ECO HP 41ECO HP 48ECO HP 55

Other codes on the same units

  • E0 Water flow fault (E8 three times)
  • E2 Communication fault between wired controller and indoor unit
  • E5 Outdoor coil temperature sensor (T3) fault
  • E6 Outdoor air temperature sensor (T4) fault
  • E7 Buffer tank temperature sensor (Tbt1) fault
  • E8 Water flow fault
  • E9 Compressor suction temperature sensor (Th) fault
  • F1 DC bus low voltage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.34. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.