Weil-McLain · Heat pump
E8 Water flow fault
What the control is telling you
The flow switch does not see enough water flow.
Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)
Likely causes
- Shut-off valve closed
- Strainer plugged
- Air in the system
- Water pressure too low
- Pump speed too low
- Expansion tank failed
- Water circuit resistance too high for the pump
- Pump fuse or PCB fuse blown
Test and repair steps
- Make sure every shut-off valve in the water circuit is fully open.
- Clean the strainer.
- Purge air from the system (see the manual's water filling section 8.6).
- Check the gauge water pressure must be more than 12-15 psi.
- Raise the pump speed setting if needed.
- Check the expansion tank.
- Check that the pipe system is not too restrictive for the pump (manual section 9.4).
- Turn off power at the disconnect before opening the unit or touching any wiring. Then check the pump fuse and the PCB fuse.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
- E2 Communication fault between wired controller and indoor unit
- E5 Outdoor coil temperature sensor (T3) fault
- E6 Outdoor air temperature sensor (T4) fault
- E7 Buffer tank temperature sensor (Tbt1) fault
- E9 Compressor suction temperature sensor (Th) fault
- F1 DC bus low voltage
- H0 Communication fault between indoor and outdoor unit
- H1 Communication fault between main board and inverter board (outdoor)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.3 Error codes, p.55. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.