Weil-McLain · Heat pump
P1 High pressure protection
What the control is telling you
The heat pump system tripped on high refrigerant pressure.
Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)
Likely causes
- Heating/DHW: low water flow, high water temperature, or air in the water loop
- Heating/DHW: water pressure too low
- Refrigerant overcharge
- Electronic expansion valve stuck, or its coil connector loose
- Cooling: coil cover left on, or outdoor coil dirty/blocked
Test and repair steps
- R32 (A2L) refrigerant only a tech qualified for flammable refrigerant should open the refrigerant circuit.
- Heating or DHW mode purge air from the water loop and check water flow.
- Check the pressure/temperature gauge. Water pressure must be more than 12-15 psi.
- Tap the expansion valve body. Unplug and plug the valve coil connector a few times and check that the valve moves.
- Cooling mode make sure the coil protector/cover was removed at install, and clean the outdoor coil.
- Check the charge. If it is overcharged, recover and weigh in the right amount.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
- L7 Phase loss protection
- L8 Compressor speed changed more than 15 Hz in one second
- L9 Compressor speed off target by more than 15 Hz
- P0 Low pressure protection
- P3 AC current protection
- P4 Compressor discharge temperature too high
- P5 Water temperature difference too high (Tw_out - Tw_in)
- P6 Inverter module protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.37. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.