L8 Compressor speed changed more than 15 Hz in one second
What the control is telling you
Compressor frequency jumped by more than 15 Hz within one second.
Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)
Likely causes
- System pressure problem
- Compressor winding fault
- U-V-W leads loose or in the wrong order
- L1-L2-L3 leads to the filter board loose
- Inverter board failed
Test and repair steps
- R32 (A2L) refrigerant only a tech qualified for flammable refrigerant should open the refrigerant circuit.
- Inverter board can hold a charge power off and wait before touching it.
- Check system pressures.
- Measure compressor winding (phase) resistance.
- Check the U, V, W compressor leads between the inverter board and the compressor, and their order.
- Check the L1, L2, L3 leads between the inverter board and the filter board.
- If all of that is good, check or replace the inverter board.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.38. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.