Weil-McLain · Heat pump
P3 AC current protection
What the control is telling you
Current draw on the supply went over the limit.
Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)
Likely causes
- Same causes as P1 (high pressure)
- Supply voltage too low
Test and repair steps
- Do the P1 checks.
- Measure supply voltage and bring it into the rated range.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
- L8 Compressor speed changed more than 15 Hz in one second
- L9 Compressor speed off target by more than 15 Hz
- P0 Low pressure protection
- P1 High pressure protection
- P4 Compressor discharge temperature too high
- P5 Water temperature difference too high (Tw_out - Tw_in)
- P6 Inverter module protection
- CL Water pump communication wire fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.37. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.