Weil-McLain · Heat pump

P0 Low pressure protection

High severity Weil-McLain ECO HP

What the control is telling you

The heat pump system tripped on low refrigerant pressure.

Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)

Likely causes

  • Low refrigerant charge
  • Outdoor coil dirty or blocked (heating or DHW mode)
  • Water flow too low (cooling mode)
  • Electronic expansion valve stuck, or its coil connector loose

Test and repair steps

  1. R32 (A2L) refrigerant only a tech qualified for flammable refrigerant should open the refrigerant circuit.
  2. Heating or DHW mode clean the outdoor coil and clear anything blocking it.
  3. Cooling mode check water flow and bring it up.
  4. Tap the expansion valve body. Unplug and plug the valve coil connector a few times so it seats well, and check that the valve moves.
  5. Leak check. If the system is short, find the leak and add refrigerant.

Models that show this code

3 models in Weil-McLain ECO HP

ECO HP 41ECO HP 48ECO HP 55

Other codes on the same units

  • L5 Zero speed protection
  • L7 Phase loss protection
  • L8 Compressor speed changed more than 15 Hz in one second
  • L9 Compressor speed off target by more than 15 Hz
  • P1 High pressure protection
  • P3 AC current protection
  • P4 Compressor discharge temperature too high
  • P5 Water temperature difference too high (Tw_out - Tw_in)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.36. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.