Weil-McLain · Heat pump

P5 Water temperature difference too high (Tw_out - Tw_in)

High severity Weil-McLain ECO HP

What the control is telling you

Outlet minus inlet water temperature is too high, which points to low water flow.

Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)

Likely causes

  • Shut-off valve closed
  • Strainer plugged
  • Air in the system
  • Water pressure too low
  • Pump speed too low
  • Expansion tank failed
  • Water circuit too restrictive for the pump

Test and repair steps

  1. Make sure every shut-off valve is fully open.
  2. Clean the strainer.
  3. Purge air from the system (manual section 8.6).
  4. Check the gauge cold water pressure should be 12-15 psi.
  5. Raise the pump speed if needed.
  6. Check the expansion tank.
  7. Check the pipe system against the pump curve (manual section 9.4).

Models that show this code

3 models in Weil-McLain ECO HP

ECO HP 41ECO HP 48ECO HP 55

Other codes on the same units

  • P0 Low pressure protection
  • P1 High pressure protection
  • P3 AC current protection
  • P4 Compressor discharge temperature too high
  • P6 Inverter module protection
  • CL Water pump communication wire fault
  • EA Compressor discharge temperature sensor (Tp) fault
  • EE Hydro-box PCB EEPROM fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.3 Error codes, p.56. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.