Weil-McLain · Heat pump
P5 Water temperature difference too high (Tw_out - Tw_in)
What the control is telling you
Outlet minus inlet water temperature is too high, which points to low water flow.
Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)
Likely causes
- Shut-off valve closed
- Strainer plugged
- Air in the system
- Water pressure too low
- Pump speed too low
- Expansion tank failed
- Water circuit too restrictive for the pump
Test and repair steps
- Make sure every shut-off valve is fully open.
- Clean the strainer.
- Purge air from the system (manual section 8.6).
- Check the gauge cold water pressure should be 12-15 psi.
- Raise the pump speed if needed.
- Check the expansion tank.
- Check the pipe system against the pump curve (manual section 9.4).
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.3 Error codes, p.56. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.