Weil-McLain · Heat pump
EA Compressor discharge temperature sensor (Tp) fault
What the control is telling you
The control reads a bad signal from the Tp sensor (discharge line).
Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)
Likely causes
- Tp connector loose
- Water in the connector
- Tp sensor failed
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching any wiring.
- Find the Tp connector and push it fully home.
- Look for water or moisture in the Tp connector. Dry it out and seal it with waterproof adhesive.
- If the connector is good and the code stays, replace the Tp sensor.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
- P4 Compressor discharge temperature too high
- P5 Water temperature difference too high (Tw_out - Tw_in)
- P6 Inverter module protection
- CL Water pump communication wire fault
- EE Hydro-box PCB EEPROM fault
- EL Communication fault between hydraulic module and MH-kit
- Eb Solar panel temperature sensor (Tsolar) fault
- Ed Water inlet temperature sensor (Tw_in) fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.35. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.