Weil-McLain · Heat pump

EA Compressor discharge temperature sensor (Tp) fault

Medium severity Weil-McLain ECO HP

What the control is telling you

The control reads a bad signal from the Tp sensor (discharge line).

Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)

Likely causes

  • Tp connector loose
  • Water in the connector
  • Tp sensor failed

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching any wiring.
  2. Find the Tp connector and push it fully home.
  3. Look for water or moisture in the Tp connector. Dry it out and seal it with waterproof adhesive.
  4. If the connector is good and the code stays, replace the Tp sensor.

Models that show this code

3 models in Weil-McLain ECO HP

ECO HP 41ECO HP 48ECO HP 55

Other codes on the same units

  • P4 Compressor discharge temperature too high
  • P5 Water temperature difference too high (Tw_out - Tw_in)
  • P6 Inverter module protection
  • CL Water pump communication wire fault
  • EE Hydro-box PCB EEPROM fault
  • EL Communication fault between hydraulic module and MH-kit
  • Eb Solar panel temperature sensor (Tsolar) fault
  • Ed Water inlet temperature sensor (Tw_in) fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.35. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.