Weil-McLain · Heat pump
Ed Water inlet temperature sensor (Tw_in) fault
What the control is telling you
The control reads a bad signal from the Tw_in sensor (plate heat exchanger water inlet).
Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)
Likely causes
- Tw_in connector loose
- Water in the connector
- Tw_in sensor failed
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching any wiring.
- Measure the Tw_in sensor resistance and compare to a known-good reading.
- Find the Tw_in connector and push it fully home.
- Look for water or moisture in the Tw_in connector. Dry it out and seal it with waterproof adhesive.
- If the connector is good and the code stays, replace the Tw_in sensor.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
- EA Compressor discharge temperature sensor (Tp) fault
- EE Hydro-box PCB EEPROM fault
- EL Communication fault between hydraulic module and MH-kit
- Eb Solar panel temperature sensor (Tsolar) fault
- HA Water outlet temperature sensor (Tw_out) fault
- HE Communication fault with Ta / room thermostat transfer board
- HF Outdoor unit EEPROM fault
- HH H6 fan fault 10 times in 120 minutes
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.3 Error codes, p.55. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.