Weil-McLain · Heat pump

HE Communication fault with Ta / room thermostat transfer board

Low severity Weil-McLain ECO HP

What the control is telling you

RT/Ta PCB is turned on in the user interface, but the thermostat transfer board is missing or not talking to the main board.

Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)

Likely causes

  • Transfer board not installed while RT/Ta PCB is set to valid
  • Communication wire between transfer board and main board loose
  • Electrical or magnetic interference

Test and repair steps

  1. If no transfer board is used, set RT/Ta PCB to invalid in the user interface.
  2. Turn off power at the disconnect before opening the unit or touching any wiring. If the board is needed, connect it to the main board and check the communication wire.
  3. Keep the wire away from high voltage and strong magnetic sources.

Models that show this code

3 models in Weil-McLain ECO HP

ECO HP 41ECO HP 48ECO HP 55

Other codes on the same units

  • EL Communication fault between hydraulic module and MH-kit
  • Eb Solar panel temperature sensor (Tsolar) fault
  • Ed Water inlet temperature sensor (Tw_in) fault
  • HA Water outlet temperature sensor (Tw_out) fault
  • HF Outdoor unit EEPROM fault
  • HH H6 fan fault 10 times in 120 minutes
  • HP Low pressure in cooling, 3 times in an hour
  • Hb PP three times and Tw_out under 44.6 F

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.3 Error codes, p.57. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.