Weil-McLain · Heat pump
HE Communication fault with Ta / room thermostat transfer board
What the control is telling you
RT/Ta PCB is turned on in the user interface, but the thermostat transfer board is missing or not talking to the main board.
Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)
Likely causes
- Transfer board not installed while RT/Ta PCB is set to valid
- Communication wire between transfer board and main board loose
- Electrical or magnetic interference
Test and repair steps
- If no transfer board is used, set RT/Ta PCB to invalid in the user interface.
- Turn off power at the disconnect before opening the unit or touching any wiring. If the board is needed, connect it to the main board and check the communication wire.
- Keep the wire away from high voltage and strong magnetic sources.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
- EL Communication fault between hydraulic module and MH-kit
- Eb Solar panel temperature sensor (Tsolar) fault
- Ed Water inlet temperature sensor (Tw_in) fault
- HA Water outlet temperature sensor (Tw_out) fault
- HF Outdoor unit EEPROM fault
- HH H6 fan fault 10 times in 120 minutes
- HP Low pressure in cooling, 3 times in an hour
- Hb PP three times and Tw_out under 44.6 F
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.3 Error codes, p.57. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.