Weil-McLain · Heat pump

HF Outdoor unit EEPROM fault

Medium severity Weil-McLain ECO HP

What the control is telling you

The outdoor unit cannot read good data from its EEPROM.

Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)

Likely causes

  • Bad EEPROM data
  • EEPROM chip failed
  • Inverter module board failed

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching any wiring.
  2. Rewrite the EEPROM data.
  3. If that does not fix it, replace the EEPROM chip.
  4. Still there replace the inverter module board.

Models that show this code

3 models in Weil-McLain ECO HP

ECO HP 41ECO HP 48ECO HP 55

Other codes on the same units

  • Eb Solar panel temperature sensor (Tsolar) fault
  • Ed Water inlet temperature sensor (Tw_in) fault
  • HA Water outlet temperature sensor (Tw_out) fault
  • HE Communication fault with Ta / room thermostat transfer board
  • HH H6 fan fault 10 times in 120 minutes
  • HP Low pressure in cooling, 3 times in an hour
  • Hb PP three times and Tw_out under 44.6 F
  • PP Tw_out - Tw_in reading not normal

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.36. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.